{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-7JP36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-7JP36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-7JP36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-7JP36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-7JP36-0AA0, molded case circuit breaker, 3-pole, 100 A continuous current, ETU550 electronic trip unit, line protection design.","salesMarkdown":"That matters when you're trying to keep a single fault from dropping half the plant. This breaker carries a 330 kA interrupting rating at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3 kA at 690 V. The sharp drop to 3 kA at 690 V tells you this is a 600 V class breaker; it's not intended for 690 V distribution duty. Front IP40 protection keeps dust and accidental contact out of the trip unit and terminals, but it's not sealed against washdown — mount it inside a cabinet, not in a wet location. ## Trip unit and adjustment range The breaker's minimum trip setting is 150 A and maximum is 1 200 A, which covers the short-time and instantaneous pickup ranges. For a 100 A feeder, you'd typically set the long-time pickup around 100 A (the rated value), short-time at maybe 400-600 A for selectivity with downstream 20-30 A branch breakers, and instantaneous at 800-1200 A to clear bolted faults fast. The ETU550 also supports communication functions — you can read trip events and settings over a bus if the panel is wired for it.","metaTitle":"Siemens 3VA2010-7JP36-0AA0 SENTRON MCCB, 100 A, ETU550, 3-Po","metaDescription":"Siemens SENTRON 3VA2010-7JP36-0AA0 molded case circuit breaker. 100 A continuous, ETU550 electronic trip, 3-pole. Interrupting rating 330 kA at 240 V. Current lifecycle stage. Quot","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"7.7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3b237d033ab4e49220bf24a930e73667.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=202274&mlfb=3VA2010-7JP36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-7JP36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting rating of 3VA2010-7JP36-0AA0 at 480 V?","answer":"The interrupting rating at 440 V is 242 kA, which is the closest published figure for a 480 V system. At 500 V it is 187 kA, and at 690 V it drops to 3 kA."},{"question":"How do I get pricing and availability for 3VA2010-7JP36-0AA0?","answer":"Submit an RFQ through this listing. We source this part through independent distribution and confirm current pricing and availability at quote time — no stock count or lead-time number is published here."},{"question":"What is the difference between 3VA2010-7JP36-0AA0 and the 5SQ2370-2YA05?","answer":"The 5SQ2370-2YA05 is a functionally similar SENTRON MCCB but from a different frame series. The 3VA2010-7JP36-0AA0 uses the ETU550 electronic trip unit; the 5SQ series may carry a different trip technology or frame size. Physical dimensions and mounting footprint may differ — verify panel cutout dimensions before substituting one for the other."},{"question":"What compliance documentation does this breaker carry?","answer":"As a Siemens SENTRON product, the 3VA2010-7JP36-0AA0 is designed to meet IEC 60947-2 and UL 489 standards for molded case circuit breakers. RoHS and REACH compliance documentation is available from Siemens. The front IP40 protection rating is listed on the nameplate."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-7JP36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-7JP36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}