{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-8JP36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-8JP36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-8JP36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-8JP36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, Molded case circuit breaker, 3VA2010-8JP36-0AA0, 3-pole, 100 A, ETU550 electronic trip unit, line protection, 440 kA at 240 V.","salesMarkdown":"That matters for selectivity coordination downstream — you can shape the trip response to keep a branch fault from taking out the whole feeder. The communication function onboard means this breaker can report status and trip events to a higher-level control system, which is useful for remote monitoring or predictive maintenance on a critical line. Breaking capacity is the headline spec for an MCCB: this one delivers 440 kA at 240 V, 330 kA at 415 V and 440 V, 220 kA at 500 V, and 52.5 kA at 690 V. The 3-pole construction suits three-phase feeders. Front-side IP40 protection means tools or fingers won't contact live parts from the front, but the breaker is not sealed against dust ingress — it belongs inside an enclosure, not in a washdown area. ## Panel fit and footprint If you are replacing an older 3VA1 frame breaker, check the mounting hole pattern; the 3VA2 frame shares the same 105 mm width but verify the depth clearance against your existing backpanel.","metaTitle":"Siemens 3VA2010-8JP36-0AA0 SENTRON MCCB, 100 A, 3-Pole, ETU5","metaDescription":"Siemens SENTRON 3VA2010-8JP36-0AA0 molded case circuit breaker, 100 A continuous, 3-pole, ETU550 electronic trip unit. Breaking capacity 440 kA at 240 V. Current production. Quoted","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"440 kA","at 415 V":"330 kA","at 440 V":"330 kA","at 500 V":"220 kA","at 690 V":"52.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"7.7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"L","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b807b65e5b7b4237cc9b5eff1a3a0b8e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=351198&mlfb=3VA2010-8JP36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-8JP36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-8JP36-0AA0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent industrial distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, not listed here."},{"question":"What is the closest functional second-source to 3VA2010-8JP36-0AA0?","answer":"The 3VA1110-5EF32-0AM0 is a different frame size (3VA1 vs 3VA2) with a different trip unit (ETU320 vs ETU550). The 3VA2 frame carries higher breaking capacities and the ETU550 offers more adjustable protection curves. They are not drop-in replacements — the mounting footprint and wiring scheme differ."},{"question":"Will 3VA2010-8JP36-0AA0 drop into a panel specified around 3VA1110-5EF32-0AM0 without rewiring?","answer":"No. The 3VA2 frame (this part) is physically larger than the 3VA1 frame. The width is the same 105 mm, but depth and height differ. The terminal arrangements and lug sizes may also differ. Panel modification and re-termination would be required."},{"question":"What compliance documentation does this breaker carry?","answer":"The SENTRON 3VA series carries IEC/EN 60947-2 certification for molded case circuit breakers. UL and CSA listings are standard for the North American market variants. RoHS and REACH compliance documentation is available from Siemens upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-8JP36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-8JP36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}