{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2025-5HL36-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2025-5HL36-0AB0","canonicalUrl":"https://aoctrl.com/siemens/3VA2025-5HL36-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2025-5HL36-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC frame 100, breaking capacity class M, Icu=55kA @ 415V, 3-pole, line protection ETU320 LI, In=25A, Ir=10...25A, Ii=1.5...12 x In, clamp connection, 2 auxiliary switch changeover H.","salesMarkdown":"## Breaking capacity and trip unit The 3VA2025-5HL36-0AB0 is a 3-pole IEC frame 100 MCCB from the Siemens 3VA2 series, rated for a 55 kA breaking capacity at 415 V AC — class M interrupting rating. That means it clears bolted faults up to 55 kA without external fuses, which is the spec that governs selectivity coordination in a distribution board. The ETU320 electronic trip unit is configured for LI protection (long-time and instantaneous), with overload pickup Ir adjustable from 10 A to 25 A and instantaneous pickup Ii settable from 1.5 to 12 times In. The 25 A fixed rating (In) sets the thermal-magnetic backbone; the Ir dial lets you match cable or load current without swapping the breaker body. ## Auxiliary switching and connections Termination is clamp (screw-less cage) type, sized for the frame 100 lug range. The 3VA2 family uses a common DIN-rail mount adapter; panel builders will find the footprint identical to other 3VA2 frame 100 breakers, so cutouts and busbar positions carry over.","metaTitle":"Siemens 3VA2025-5HL36-0AB0 Circuit Breaker, 55kA @ 415V, 25A","metaDescription":"Siemens 3VA2025-5HL36-0AB0 IEC frame 100 circuit breaker, 55kA breaking capacity at 415V, 3-pole, ETU320 LI trip unit, 25A adjustable overload, 2 changeover aux switches. Current p","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1415563&mlfb=3VA2025-5HL36-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2025-5HL36-0AB0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this breaker?","answer":"Icu is 55 kA at 415 V AC, which is the class M interrupting rating on the 3VA2 IEC frame 100 platform."},{"question":"What trip unit does this 3VA2025-5HL36-0AB0 have?","answer":"It uses the ETU320 electronic trip unit with LI protection: long-time overload pickup Ir adjustable 10–25 A and instantaneous pickup Ii adjustable 1.5–12 x In."},{"question":"Where can I buy 3VA2025-5HL36-0AB0 and how is it quoted?","answer":"This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock count or price is listed here."},{"question":"Does this breaker include auxiliary switches?","answer":"Yes, it ships with two changeover auxiliary switches (H designation), providing two Form C contacts for status feedback."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2025-5HL36-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2025-5HL36-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}