{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2025-7HL36-0AC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2025-7HL36-0AC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2025-7HL36-0AC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2025-7HL36-0AC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC frame 100, breaking capacity class C, 3-pole circuit breaker, 25 A, ETU320 LI, 110 kA @ 415 V, clamp connection, 2 auxiliary switches.","salesMarkdown":"## What the 110 kA rating means for your panel The Siemens 3VA2025-7HL36-0AC0 is a 3-pole IEC frame 100 circuit breaker with a 110 kA breaking capacity at 415 V — that is class C interrupting rating. For a main or feeder breaker on a high-fault industrial service, that SCCR headroom lets you avoid cascading an upstream trip or adding current-limiting fuses. The ETU320 LI trip unit gives you adjustable overload protection (Ir) from 10 to 25 A and short-circuit pickup (Ii) from 1.5 to 12 times the In of 25 A. ## Panel and wiring integration Clamp connection terminals — no lugs or compression tools needed, just strip and torque. The 3VA2 frame 100 footprint is standard for Siemens IEC panels; it clips onto the DIN rail or mounts with screws on a mounting plate. Two HQ auxiliary switches are built in, so you get status feedback without adding a separate accessory block.","metaTitle":"Siemens 3VA2025-7HL36-0AC0 Circuit Breaker, 110 kA @ 415 V","metaDescription":"Siemens 3VA2025-7HL36-0AC0 IEC frame 100 breaker, 25 A, ETU320 LI trip, 110 kA breaking capacity @ 415 V. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1124598&mlfb=3VA2025-7HL36-0AC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2025-7HL36-0AC0/alternatives.json"},"ai":{"faq":[{"question":"What trip unit and adjustments does this breaker have?","answer":"It has an ETU320 LI (line protection) trip unit. Overload protection Ir is adjustable from 10 to 25 A, and short-circuit pickup Ii is adjustable from 1.5 to 12 times the 25 A In. No ground-fault or short-delay functions."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2025-7HL36-0AC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2025-7HL36-0AC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}