{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2025-7JP32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2025-7JP32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2025-7JP32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2025-7JP32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2025-7JP32-0AA0, molded case circuit breaker, 3-pole, 25 A, ETU550 electronic trip unit, 330 kA at 240 V.","salesMarkdown":"## What this MCCB brings to a panel The ETU550 electronic trip unit gives you adjustable long-time delay (tr 0.5–25 s) and short-time delay (tsd up to 0.5 s), which means you can coordinate selectivity downstream without sacrificing fault clearance speed. Breaking capacity hits 330 kA at 240 V and 242 kA at 415/440 V, so it handles high-fault utility feeds or transformer secondaries without cascading upstream. Three-pole construction, line protection version — this is the main feeder or large subfeed breaker in an industrial distribution panel. The 0.84 W maximum power loss means negligible heat contribution to the enclosure thermal budget. Long-time pickup is fixed at the 25 A rated current; short-time delay adjustable up to 0.5 s lets you ride through motor-start inrush or transformer magnetizing current without nuisance tripping.","metaTitle":"Siemens 3VA2025-7JP32-0AA0 SENTRON MCCB, 25 A, 3-pole, ETU55","metaDescription":"Siemens SENTRON 3VA2025-7JP32-0AA0 molded case circuit breaker, 25 A rated, 3-pole, ETU550 electronic trip unit, 330 kA at 240 V. Current lifecycle stage. Sourced to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3 kA","at 40 °C":"25 A","at 45 °C":"25 A","at 50 °C":"25 A","at 55 °C":"25 A","at 60 °C":"25 A","at 65 °C":"25 A","at 70 °C":"25 A","Depth [in]":"3.4 in","Width [in]":"4.1 in","Height [in]":"7.1 in","Number of poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"0.84 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-40 °C","Other Measurement Function":"No","Rated continuous current Iu":"25 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU550","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"25","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"25 A","Adjustable response value current / li max.":"300 A","Adjustable response value current / li min.":"38 A","Adjustable response value current / lr min.":"10 A","Adjustable response value current / Isd max.":"250 A","Adjustable response value current / Isd min.":"15 A","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"C","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/04658e8773f5ab18b97c270053474b97.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=260425&mlfb=3VA2025-7JP32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2025-7JP32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2025-7JP32-0AA0?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer."},{"question":"Will 3VA2025-7JP32-0AA0 drop into a panel specified around 5SQ2370-2YA05?","answer":"The 3VA2025-7JP32-0AA0 is a different platform (SENTRON 3VA2 with ETU550 electronic trip) versus the 5SQ2370-2YA05 series. While both are 3-pole MCCBs, the footprint, mounting hole pattern, and accessory compatibility differ — verify panel cutout dimensions and bus-bar spacing before substituting. The 105 mm width and 181 mm height are standard for this class, but the 5SQ2370 series may use a different mounting center."},{"question":"What compliance documentation is available for this breaker?","answer":"As a Siemens SENTRON MCCB, the 3VA2025-7JP32-0AA0 carries CE marking for the European market and is designed to meet IEC 60947-2. RoHS and REACH declarations are standard from Siemens for current-production 3VA2 series devices. UL/CSA listings vary by specific variant — confirm with the order code suffix or request the manufacturer's declaration at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2025-7JP32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2025-7JP32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}