{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2025-8HL32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2025-8HL32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2025-8HL32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2025-8HL32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series molded case circuit breaker, 3VA2025-8HL32-0AA0, 3-pole, 25 A rated continuous current, ETU320 electronic overcurrent release, line protection design.","salesMarkdown":"The ETU320 gives you adjustable thermal and magnetic trip settings, so you can dial it in for the load without swapping the breaker. This is a current-production part (lifecycle stage is active), so it's still the standard build for new panels, not a legacy item you're hunting down on surplus shelves. At 240 V it interrupts up to 440 kA; at 415 V that drops to 330 kA, and at 690 V it still handles 52.5 kA. That matters when you're packing breakers into a tight panel next to transformers or drives that throw heat.","metaTitle":"Siemens 3VA2025-8HL32-0AA0 SENTRON MCCB, 25A, 3-Pole, ETU320","metaDescription":"Siemens SENTRON 3VA2025-8HL32-0AA0 molded case circuit breaker. 25A rated current, 3-pole, ETU320 electronic trip unit. Interrupting capacity up to 440kA at 240V. Active production","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"300 A","Minimum":"38 A","at 240 V":"440 kA","at 415 V":"330 kA","at 440 V":"330 kA","at 500 V":"220 kA","at 690 V":"52.5 kA","at 40 °C":"25 A","at 45 °C":"25 A","at 50 °C":"25 A","at 55 °C":"25 A","at 60 °C":"25 A","at 65 °C":"25 A","at 70 °C":"25 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"0.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"25 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"L","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ada32687bd0c6b894d56c759e689b745.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=525487&mlfb=3VA2025-8HL32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2025-8HL32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2025-8HL32-0AA0 and how do I get a price?","answer":"We source and quote this breaker to order against an RFQ. Send us your quantity and target delivery window; we'll confirm availability and current pricing at quote time — no automated stock figures here."},{"question":"What is the interrupting capacity of this MCCB at different voltages?","answer":"At 240 V it interrupts 440 kA; at 415 V and 440 V it handles 330 kA; at 500 V it's 220 kA; and at 690 V it still clears 52.5 kA."},{"question":"What trip unit does the 3VA2025-8HL32-0AA0 use?","answer":"It uses the ETU320 electronic overcurrent release, which provides adjustable thermal and magnetic trip settings for line-protection applications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2025-8HL32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2025-8HL32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}