{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2063-5HL36-0CL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2063-5HL36-0CL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2063-5HL36-0CL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2063-5HL36-0CL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker (MCCB), 3VA2063-5HL36-0CL0, 63 A continuous, 3-pole, line protection, with undervoltage release.","salesMarkdown":"## Siemens 3VA2063-5HL36-0CL0 — SENTRON MCCB, 63 A, 3-Pole, Line Protection The Siemens 3VA2063-5HL36-0CL0 is a SENTRON molded case circuit breaker (MCCB) rated for 63 A continuous current across the full ambient range of -25 °C to 70 °C, with no derating required up to 70 °C. The interrupting ratings are substantial: 187 kA at 240 V AC, 121 kA at 415/440 V, 75.6 kA at 500 V, and 3 kA at 690 V — so it handles high-fault utility feeds without cascading upstream breakers. That gives four separate signal paths for PLC or SCADA monitoring without adding external interposing relays. Dimensions are 105 mm wide by 181 mm tall by 86 mm deep — a standard 3-pole MCCB footprint for the SENTRON 3VA2 frame. Panel cutout and busbar spacing match the 3VA2 family; if you are replacing a 3VA1 or 3VA0 unit, check the mounting hole pattern because the 3VA2 frame is slightly wider than the 3VA1. The 63 A continuous rating is flat across the entire operating temperature range — no derating curve to watch for. The adjustable thermal-magnetic trip unit (implied by the 95 A minimum and 756 A maximum range) allows the breaker to be set for cable protection at the lower end or for a specific overload threshold. The 3 kA at 690 V is the limit for the few 690 V line-to-line systems (some mining and marine plants); for most 400/480 V panels, the 121 kA rating is the one that matters. The undervoltage release is a factory-installed option on this order code — not a field-addable kit. If your BOM requires a UVR, this exact code is the one; the base 3VA2063-5HL36-0AA0 (without UVR) is a different variant. The auxiliary switch configuration (2 aux + 1 trip alarm + 1 electrical alarm HQ) provides four isolated contacts for status feedback, which is more than the standard 1 aux + 1 alarm found on many MCCBs. That extra alarm contact (HQ) is typically wired to a separate alarm annunciator or a safety PLC input.","metaTitle":"Siemens 3VA2063-5HL36-0CL0 SENTRON MCCB, 63 A, 3-Pole, 187 k","metaDescription":"Siemens 3VA2063-5HL36-0CL0 SENTRON molded case circuit breaker, 63 A, 3-pole, 187 kA interrupting at 240 V. Line protection with UVR. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"756 A","Minimum":"95 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"7.9 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20635HL360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=439525&mlfb=3VA2063-5HL36-0CL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2063-5HL36-0CL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2063-5HL36-0CL0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer."},{"question":"What is 3VA2063-5HL36-0CL0's listed depth (86 mm) on this component line?","answer":"The depth is 86 mm (3.39 in). The width is 105 mm (4.13 in) and the height is 181 mm (7.13 in). These are the standard 3VA2 3-pole frame dimensions."},{"question":"What compliance documentation does this brand provide for 3VA2063-5HL36-0CL0?","answer":"As a Siemens SENTRON MCCB, it carries the usual IEC/EN 60947-2 and UL 489 certifications for molded case circuit breakers. RoHS and REACH declarations are available from Siemens documentation. Specific compliance documents (CE, UKCA, EAC) should be confirmed at quote time for your jurisdiction."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2063-5HL36-0CL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2063-5HL36-0CL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}