{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2063-5HL36-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2063-5HL36-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2063-5HL36-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2063-5HL36-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2063-5HL36-0HA0, molded case circuit breaker, 3-pole, 63 A, ETU320 electronic trip unit, shunt trip, 187 kA at 240 V.","salesMarkdown":"The interrupting ratings tell the real story: 187 kA at 240 V AC, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 3.4 kA at 690 V. At 690 V the 3.4 kA figure reflects the reduced arc-quenching capability at higher voltage; this breaker is sized for 400–500 V distribution, not 690 V main feeds. The ETU320 release provides adjustable thermal and magnetic protection curves, giving the panel designer selectivity headroom downstream. The 63 A rating holds flat from 40 °C to 50 °C ambient, then derates to 60.6375 A at 55 °C, 58.275 A at 60 °C, 55.9125 A at 65 °C, and 53.55 A at 70 °C. In a 50 °C panel enclosure, you get the full 63 A; above that, the derating curve governs continuous load. It is a straightforward line-protection MCCB with a voltage-trigger capability for emergency-off or remote-disconnect circuits. ## Panel fit and mechanical data The 3VA2063-5HL36-0HA0 measures 105 mm wide, 181 mm high, and 86 mm deep — a standard SENTRON 3VA frame that mounts on a DIN rail or panel-mount plate. The 3-pole footprint matches the 3VA family cutout; if you are replacing a 3VA1010-2ED32-0JA0, the width and depth are identical, so the panel layout does not need rework. Maximum power loss is 5.4 W, which is negligible for enclosure thermal budgeting.","metaTitle":"Siemens 3VA2063-5HL36-0HA0 SENTRON MCCB, 63 A, 187 kA at 240","metaDescription":"Siemens SENTRON 3VA2063-5HL36-0HA0 molded case circuit breaker, 63 A rated, 3-pole, ETU320 release, 187 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"3.4 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.6375 A","at 60 °C":"58.275 A","at 65 °C":"55.9125 A","at 70 °C":"53.55 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"5.4 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2063-5HL36-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"756 A","Adjustable response value current / li min.":"95 A","Adjustable response value current / lr min.":"25 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=397022&mlfb=3VA2063-5HL36-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2063-5HL36-0HA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting rating of 3VA2063-5HL36-0HA0 at 415 V?","answer":"121 kA at 415 V AC. The same rating applies at 440 V. At 240 V it reaches 187 kA, and at 500 V it is 79 kA."},{"question":"Will 3VA2063-5HL36-0HA0 drop into a panel specified for 3VA1010-2ED32-0JA0?","answer":"Yes, the 105 mm width and 86 mm depth are shared across the 3VA frame family, so the panel cutout and DIN-rail position are compatible. The 3VA2063 is a higher-interrupting-capacity frame (187 kA vs the 3VA1010's typical 25–65 kA range), so verify the downstream coordination study still holds."},{"question":"What compliance documentation does this MCCB carry?","answer":"Siemens provides a declaration of conformity to IEC 60947-2 for the SENTRON 3VA series. CE marking is standard. RoHS and REACH compliance documentation is available from Siemens on request."},{"question":"Where can I buy 3VA2063-5HL36-0HA0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — think landed, not list, and the paperwork will be clean for customs clearance."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2063-5HL36-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2063-5HL36-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}