{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2063-5HN32-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2063-5HN32-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2063-5HN32-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2063-5HN32-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON, Molded case circuit breaker, 3VA2063-5HN32-0DA0, 3-pole, 63 A continuous, 187 kA interrupting at 240 V, undervoltage release, line protection design.","salesMarkdown":"The Siemens SENTRON 3VA2063-5HN32-0DA0 is a 3-pole molded case circuit breaker rated for 63 A continuous current across the full operating temperature range from -25 °C to 70 °C, with no derating needed up to 70 °C. The 187 kA at 240 V is the headline number, but the real-world curve matters more: 121 kA at 415 V and 75.6 kA at 500 V, dropping to 3 kA at 690 V. If you're feeding a 600 V delta service, this breaker is within its insulation envelope. The 3VA2063-5HN32-0DA0 measures 105 mm wide, 181 mm tall, and 86 mm deep — a standard 3-pole MCCB footprint that mounts on a DIN rail or direct panel. Power loss is 7.9 W maximum, which is manageable in a sealed enclosure but worth checking if you're packing six of these side-by-side at 40 °C ambient.","metaTitle":"Siemens 3VA2063-5HN32-0DA0 SENTRON MCCB, 63 A, 3-pole, 187 k","metaDescription":"Siemens 3VA2063-5HN32-0DA0 SENTRON molded case circuit breaker, 63 A continuous, 3-pole, 187 kA interrupting at 240 V, undervoltage release, current lifecycle. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"756 A","Minimum":"756 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"7.9 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20635HN320AA0","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=54550&mlfb=3VA2063-5HN32-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2063-5HN32-0DA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2063-5HN32-0DA0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is 3VA2063-5HN32-0DA0's interrupting capacity at different voltages?","answer":"187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V."},{"question":"What compliance documentation does this breaker carry?","answer":"The SENTRON 3VA series carries UL 489, CSA C22.2 No. 5, and IEC 60947-2 certifications. RoHS and REACH compliance documentation is available from Siemens."},{"question":"Will 3VA2063-5HN32-0DA0 drop into a panel specified around 3VA2116-5JP32-0AE0?","answer":"Both are 3-pole SENTRON 3VA frames with the same 105 mm width and DIN-rail mounting, so physical fit is identical. The key difference is the continuous current rating — this one is 63 A, the 3VA2116-5JP32-0AE0 is a higher-current frame. If your BOM calls for 63 A, this is a direct drop-in without rewiring."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2063-5HN32-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2063-5HN32-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}