{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2063-5HN36-0DL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2063-5HN36-0DL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2063-5HN36-0DL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2063-5HN36-0DL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC frame 100, breaking capacity class M, 3-pole, line protection ETU350 LSI, In=63A, Icu=55kA @ 415V, clamp connection, undervoltage release 208-230V AC, 2 auxiliary switches HQ, 1 trip alarm switch HQ, 1 electrical alarm switch.","salesMarkdown":"The rated current In is 63 A, with overload protection Ir adjustable from 25 A to 63 A, short-time pickup Isd from 1.5 to 10 times Ir, and instantaneous pickup Ii fixed at 12 times In. This matters for selectivity: you can coordinate it downstream of a higher-rated upstream breaker to clear a fault without taking the whole panel out. ## Built-in accessories and wiring note The clamp connection terminals accept copper conductors without lugs, which speeds panel wiring. All accessories are factory-installed; no field-kit assembly required.","metaTitle":"Siemens 3VA2063-5HN36-0DL0 Circuit Breaker, 63A ETU350 LSI,","metaDescription":"Siemens 3VA2063-5HN36-0DL0 IEC 3VA2 frame 100 breaker, 3-pole, 63A, ETU350 LSI, 55kA @ 415V. Current production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=278233&mlfb=3VA2063-5HN36-0DL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2063-5HN36-0DL0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this breaker?","answer":"The ultimate breaking capacity Icu is 55 kA at 415 V AC, which is the 'M' breaking class for the 3VA2 frame."},{"question":"Where can I buy 3VA2063-5HN36-0DL0 and get pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2063-5HN36-0DL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2063-5HN36-0DL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}