{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2063-5JQ32-0AC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2063-5JQ32-0AC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2063-5JQ32-0AC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2063-5JQ32-0AC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2063-5JQ32-0AC0, molded case circuit breaker, 3-pole, 63 A, 187 kA interrupting capacity at 240 V AC, line protection design.","salesMarkdown":"## Interrupting capacity across voltage levels The 3VA2063-5JQ32-0AC0 delivers 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V. That 121 kA at 415 V is the figure that matters for most European industrial distribution — it tells you the breaker can clear a bolted fault on a 400 V bus without welding its contacts or venting arc gas into the enclosure. The breaker measures 105 mm wide, 181 mm tall, and 86 mm deep — a standard SENTRON 3VA2 frame footprint that drops into existing DIN-rail or screw-mounted panel layouts without re-drilling. The 86 mm depth keeps it clear of shallow enclosure doors. ## Built-in communication and auxiliary switching The supplied basic switch carries order code 3VA20635JQ320AA0 — useful for cross-referencing replacement internal assemblies. ## Thermal performance and power loss The 63 A rating holds flat from 40 °C through 70 °C ambient — no derating curve to calculate for warm panel environments. Maximum power loss is 5.4 W, which keeps heat buildup manageable in a densely packed enclosure.","metaTitle":"Siemens 3VA2063-5JQ32-0AC0 SENTRON MCCB, 63 A, 3-Pole, 187 k","metaDescription":"Siemens SENTRON 3VA2063-5JQ32-0AC0 molded case circuit breaker, 63 A, 3-pole, 187 kA interrupting at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"756 A","Minimum":"95 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Initial Value":"16 A","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Full-Scale Value":"63 A","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"5.4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20635JQ320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU560","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 40% to 160%","Product Function / Grounding Protection":"Yes","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=141395&mlfb=3VA2063-5JQ32-0AC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2063-5JQ32-0AC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2063-5JQ32-0AC0 and get a price?","answer":"This part is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time."},{"question":"What is the interrupting capacity of 3VA2063-5JQ32-0AC0 at 240 V?","answer":"187 kA at 240 V AC, with 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V."},{"question":"What are the physical dimensions of 3VA2063-5JQ32-0AC0?","answer":"Width 105 mm, height 181 mm, depth 86 mm — a standard SENTRON 3VA2 frame footprint."},{"question":"Does 3VA2063-5JQ32-0AC0 include communication capability?","answer":"Yes, this variant has a communication function for remote monitoring, plus two auxiliary switches (HQ design) for status feedback."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2063-5JQ32-0AC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2063-5JQ32-0AC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}