{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2063-5KP32-0HH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2063-5KP32-0HH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2063-5KP32-0HH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2063-5KP32-0HH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, molded case circuit breaker, 3VA2063-5KP32-0HH0, 63 A rated continuous current, 3-pole, ETU850 electronic trip unit, line protection version, 187 kA interrupting capacity at 240 V.","salesMarkdown":"The Siemens SENTRON 3VA2063-5KP32-0HH0 is a 3-pole molded case circuit breaker rated for 63 A continuous current (Iu) at 40 °C through 50 °C, with no derating needed in that band. Interrupting capacity is what sets this frame apart: 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 3.4 kA at 690 V. The 86 mm depth stays within most enclosure clearances, but the height at 181 mm means you'll want to verify the gland plate clearance if you're replacing a shorter frame. ## Auxiliaries and communication The breaker also carries a communication function and an other measurement function, though the evidence doesn't specify protocol. Power loss is 5.4 W maximum, negligible for panel thermal budgeting.","metaTitle":"Siemens SENTRON 3VA2063-5KP32-0HH0 MCCB, 63 A, 3-Pole, ETU85","metaDescription":"Siemens SENTRON 3VA2063-5KP32-0HH0 molded case circuit breaker, 63 A rated, 3-pole, ETU850 electronic trip, 187 kA at 240 V. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"3.4 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.6375 A","at 60 °C":"58.275 A","at 65 °C":"55.9125 A","at 70 °C":"53.55 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"5.4 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2063-5KP32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"ETU850","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"25","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"756 A","Adjustable response value current / li min.":"95 A","Adjustable response value current / lr min.":"25 A","Adjustable response value current / Isd max.":"630 A","Adjustable response value current / Isd min.":"38 A","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=489914&mlfb=3VA2063-5KP32-0HH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2063-5KP32-0HH0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA2063-5KP32-0HH0's listed depth?","answer":"The depth is 86 mm, with a width of 105 mm and height of 181 mm. That 86 mm depth fits standard enclosure depths, but the 181 mm height is worth verifying against gland plate clearance in retrofit applications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2063-5KP32-0HH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2063-5KP32-0HH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}