{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2063-5KP32-0JL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2063-5KP32-0JL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2063-5KP32-0JL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2063-5KP32-0JL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, Molded case circuit breaker, 3VA2063-5KP32-0JL0, 3-pole, 63 A, line protection, 187 kA breaking capacity at 240 V AC.","salesMarkdown":"It carries a maximum breaking capacity of 187 kA at 240 V AC, stepping down to 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V — covering most industrial distribution voltages without needing a frame size bump. The adjustable thermal-magnetic trip range (95 A minimum to 756 A maximum) means this frame can be tuned for loads well below or above the 63 A continuous rating, though the 63 A continuous is the hard limit for uninterrupted service. At 415 V the 121 kA rating still covers most industrial secondary distribution. Power loss is 5.4 W maximum, low enough that ventilation spacing is standard. The 3VA2063-5KP32-0JL0 measures 105 mm wide, 181 mm high, and 86 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures without re-drilling. It includes trip and voltage indicators for quick visual status checks on the panel door.","metaTitle":"Siemens 3VA2063-5KP32-0JL0 SENTRON MCCB, 63 A, 3-Pole, 187 k","metaDescription":"Siemens 3VA2063-5KP32-0JL0 SENTRON molded case circuit breaker, 63 A continuous, 3-pole, line protection, 187 kA breaking at 240 V. Active production, sourced to order. Request quo","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"756 A","Minimum":"95 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"5.4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Of The Supplied Basic Switch":"3VA20635KP320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 40% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=454735&mlfb=3VA2063-5KP32-0JL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2063-5KP32-0JL0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2063-5KP32-0JL0 at different voltages?","answer":"At 240 V AC it breaks 187 kA, at 415 V and 440 V it breaks 121 kA, at 500 V it breaks 75.6 kA, and at 690 V it breaks 3 kA."},{"question":"Where can I buy 3VA2063-5KP32-0JL0 and how is it quoted?","answer":"This part is available to order through our independent distribution channel. Submit an RFQ for current pricing, availability, and lead time — we quote per your volume and delivery window."},{"question":"Does 3VA2063-5KP32-0JL0 include auxiliary switches and a shunt trip?","answer":"Yes, it comes with 2 auxiliary switches, 1 trip alarm switch, 1 electrical alarm switch, and a shunt trip (STL) release built in."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2063-5KP32-0JL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2063-5KP32-0JL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}