{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2063-6HL32-0AJ0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2063-6HL32-0AJ0","canonicalUrl":"https://aoctrl.com/siemens/3VA2063-6HL32-0AJ0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2063-6HL32-0AJ0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2063-6HL32-0AJ0, molded case circuit breaker, 3-pole, 63 A, 242 kA at 240 V, ETU320 electronic trip unit, line protection, IP40 front.","salesMarkdown":"It carries 63 A continuous at 40 °C and breaks up to 242 kA at 240 V — that fault-clearing capacity means it handles high-available-fault-current service entrances or sub-distribution boards without cascading upstream. The ETU320 electronic trip unit gives adjustable long-time, short-time, and instantaneous protection curves, so you can coordinate selectively with downstream breakers. At 40 °C you get the full 63 A; at 55 °C it derates to 60.6 A, and at 70 °C to 53.6 A. The 86 mm depth and 105 mm width fit standard Siemens 3VA mounting bases; the IP40 front means it's protected against tools and wires but not washdown — keep it inside a closed enclosure. The 63 A rating at 40 °C is the continuous current limit for a 3-pole MCCB protecting a feeder or large motor branch. If your available fault current is lower (common in secondary distribution), the breaker still works; you just have more headroom than needed. The 800 V rated insulation voltage (Ui) covers 480 V and 600 V class systems with margin.","metaTitle":"Siemens 3VA2063-6HL32-0AJ0 SENTRON MCCB, 63A, 242kA at 240V","metaDescription":"Siemens SENTRON 3VA2063-6HL32-0AJ0 molded case circuit breaker, 63A rated, 242kA breaking at 240V, 3-pole, ETU320, IP40 front. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.6375 A","at 60 °C":"58.275 A","at 65 °C":"55.9125 A","at 70 °C":"53.55 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"5.4 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HP","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2063-6HL32-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"756 A","Adjustable response value current / li min.":"95 A","Adjustable response value current / lr min.":"25 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB11","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=288381&mlfb=3VA2063-6HL32-0AJ0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2063-6HL32-0AJ0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2063-6HL32-0AJ0 and what is the lead time?","answer":"This MCCB is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does this brand provide for 3VA2063-6HL32-0AJ0?","answer":"Siemens SENTRON MCCBs typically carry UL, CSA, CE, and RoHS declarations; specific documentation is available on request with the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2063-6HL32-0AJ0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2063-6HL32-0AJ0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}