{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2063-6HL32-0CC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2063-6HL32-0CC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2063-6HL32-0CC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2063-6HL32-0CC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2063-6HL32-0CC0, 3-pole molded case circuit breaker, 63 A continuous, line protection design, 242 kA interrupting at 240 V.","salesMarkdown":"Three poles, 63 A frame, and interrupting ratings that climb to 242 kA at 240 V and 187 kA at 415 V. At 690 V the rating drops to 3 kA — that's the arc-extinction limit for this frame size, so if your line side runs above 500 V (121 kA at 500 V), confirm the available fault current stays under the curve. That 105 mm width is a standard 3-pole MCCB footprint — it occupies three 35 mm DIN modules worth of panel width if you're spacing by the usual 17.5 mm per pole. The UVR drops the breaker if control voltage falls below its dropout threshold — common in safety circuits where a loss of control power should open the main feeder.","metaTitle":"Siemens 3VA2063-6HL32-0CC0 SENTRON MCCB, 63A, 3-Pole, 242kA@","metaDescription":"Siemens SENTRON 3VA2063-6HL32-0CC0 molded case circuit breaker, 63A continuous, 3-pole, 242 kA interrupting at 240 V. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"756 A","Minimum":"95 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"7.9 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20636HL320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=200326&mlfb=3VA2063-6HL32-0CC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2063-6HL32-0CC0/alternatives.json"},"ai":{"faq":[{"question":"Does this breaker include an undervoltage release?","answer":"Yes, it ships with an undervoltage release (UVR) and two auxiliary switches (HQ type) installed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2063-6HL32-0CC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2063-6HL32-0CC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}