{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2063-6HL32-0HC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2063-6HL32-0HC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2063-6HL32-0HC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2063-6HL32-0HC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2063-6HL32-0HC0, molded case circuit breaker, 3-pole, 63 A continuous, 242 kA interrupting at 240 V, with shunt trip and auxiliary switches.","salesMarkdown":"It's rated for 63 A continuous current across the full ambient temperature range from -25 °C to 70 °C — no derating needed up to that ceiling, which is handy when the panel sits near hot machinery. At 240 V it interrupts 242 kA, at 415 V it's still 187 kA, so it handles serious fault currents without upstream coordination headaches. The 63 A frame is the same across the 3VA2 family, but the interrupting capacity here — 242 kA at 240 V — is the high-end option. That's enough for most secondary distribution panels fed from a large transformer or a generator bus. The 3-pole design handles three-phase loads; the shunt trip (STL) and two auxiliary switches (HQ) let you integrate remote tripping and status feedback into a PLC or safety circuit. ## Integration notes Dimensions: 181 mm high, 105 mm wide, 86 mm deep. That's a standard SENTRON 3VA2 footprint — fits existing DIN-rail or panel-mount cutouts for the series. Spring-cage terminals accept 0.2–2.5 mm² solid or ferruled stranded. The shunt trip coil draws its own power; verify polarity and voltage match the control circuit before energizing.","metaTitle":"3VA2063-6HL32-0HC0 SENTRON MCCB, 63 A, 3-Pole, 242 kA at 240","metaDescription":"Siemens SENTRON 3VA2063-6HL32-0HC0 molded case circuit breaker, 63 A continuous, 3-pole, 242 kA interrupting at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"756 A","Minimum":"95 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"5.4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20636HL320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=350697&mlfb=3VA2063-6HL32-0HC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2063-6HL32-0HC0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA2063-6HL32-0HC0's interrupting capacity at 240 V?","answer":"It interrupts 242 kA at 240 V, which is the high-interrupting option in the 3VA2 family."},{"question":"Will 3VA2063-6HL32-0HC0 drop into a panel that was specified around 3VA2163-5HL32-0JB0 without rewiring?","answer":"Mechanically it fits the same 3VA2 frame cutout, but the 3VA2063 has a higher interrupting capacity (242 kA vs the 3VA2163's lower rating). If the panel was designed for a lower fault level, swapping to this breaker requires a coordination review — don't just drop it in without checking the available fault current."},{"question":"Where can I buy 3VA2063-6HL32-0HC0?","answer":"This part is sourced to order against an RFQ through our independent distribution channel. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2063-6HL32-0HC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2063-6HL32-0HC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}