{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2063-6HL32-0JL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2063-6HL32-0JL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2063-6HL32-0JL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2063-6HL32-0JL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2063-6HL32-0JL0, molded case circuit breaker, 3-pole, 63 A, 242 kA at 240 V, ETU320 electronic trip unit, shunt trip, line protection.","salesMarkdown":"The Siemens 3VA2063-6HL32-0JL0 is a SENTRON molded case circuit breaker rated for 63 A continuous current (Iu) at 40 °C, with no derating needed up to 50 °C — it holds 63 A flat across that band. At 55 °C it derates to 60.6 A, and at 70 °C to 53.6 A, so the thermal margin matters if your enclosure runs hot. The 242 kA breaking capacity at 240 V is the headline number for high-fault panels; at 415 V it still interrupts 187 kA, and at 690 V it drops to 4 kA — that last figure governs the SCCR for 690 V bus work. A shunt trip (STL) is integrated for remote opening via a control signal. The auxiliary contact block carries two auxiliary switches plus one trip alarm and one electrical alarm switch (HQ configuration), which gives you status feedback for the PLC or annunciator without a separate module. The breaker measures 105 mm wide, 181 mm high, and 86 mm deep — a standard SENTRON 3VA frame size that fits the same DIN-rail or screw-mount footprint as other 3VA2063 variants.","metaTitle":"Siemens 3VA2063-6HL32-0JL0 SENTRON MCCB, 63 A, 242 kA at 240","metaDescription":"Siemens SENTRON 3VA2063-6HL32-0JL0 molded case circuit breaker, 63 A rated, 242 kA breaking at 240 V. ETU320 release, shunt trip. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.6375 A","at 60 °C":"58.275 A","at 65 °C":"55.9125 A","at 70 °C":"53.55 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"5.4 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2063-6HL32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"756 A","Adjustable response value current / li min.":"95 A","Adjustable response value current / lr min.":"25 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=283597&mlfb=3VA2063-6HL32-0JL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2063-6HL32-0JL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2063-6HL32-0JL0 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — stock and lead time are confirmed at quote time."},{"question":"What are the mounting dimensions of 3VA2063-6HL32-0JL0?","answer":"Width 105 mm, height 181 mm, depth 86 mm."},{"question":"What compliance documentation does Siemens provide for this MCCB?","answer":"As a SENTRON series MCCB, the 3VA2063-6HL32-0JL0 is designed to meet IEC 60947-2 and UL 489 standards. RoHS and REACH declarations are standard from Siemens. Specific certificates (UL, CSA, CE, UKCA, EAC) should be confirmed at quote time against the exact variant and destination."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2063-6HL32-0JL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2063-6HL32-0JL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}