{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2063-6HM32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2063-6HM32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2063-6HM32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2063-6HM32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2063-6HM32-0AA0, molded case circuit breaker, 3-pole, 63 A rated continuous current, 242 kA breaking capacity at 240 VAC, line protection design.","salesMarkdown":"Breaking capacity is 242 kA at 240 VAC, 187 kA at 415/440 VAC, 121 kA at 500 VAC, and 3 kA at 690 VAC. That 242 kA figure at 240 V is the headline number for high-fault panels in North American 240/120 V distribution; the 187 kA at 415 V covers European 400 V grids. For 690 V applications the 3 kA rating restricts it to low-fault branches. Maximum power loss is 5.4 W per pole — negligible for panel thermal budgeting. ## Ground-fault and protection configuration That makes it suitable for grounded-wye systems where you need GF protection integrated into the MCCB rather than a separate relay. No undervoltage release, no voltage trip, no communication function — it is a standalone thermal-magnetic breaker with GF module. The trip indicator is not fitted, so a remote status contact is absent. If your BOM requires a visual trip flag or auxiliary contact for the PLC, you will need the accessory kit separately. The storage low end matters for unheated warehouses in cold climates — the breaker can sit at -40 °C without damage as long as it is not energized.","metaTitle":"Siemens 3VA2063-6HM32-0AA0 SENTRON MCCB, 63 A, 3-Pole, 242 k","metaDescription":"Siemens SENTRON 3VA2063-6HM32-0AA0 molded case circuit breaker, 63 A continuous, 3-pole, 242 kA breaking capacity at 240 VAC. Current production. Sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"756 A","Minimum":"95 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Initial Value":"16 A","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Full-Scale Value":"63 A","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"5.4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU330","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"Yes","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LIG","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0a30d91d77a2a5c7655630d668222f99.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=430672&mlfb=3VA2063-6HM32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2063-6HM32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Does 3VA2063-6HM32-0AA0 include ground-fault protection?","answer":"Yes, it has ground-fault monitoring via summation current formation on the L-conductor — it trips on residual imbalance without needing a separate GF relay."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2063-6HM32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2063-6HM32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}