{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2063-6HN32-0BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2063-6HN32-0BA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2063-6HN32-0BA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2063-6HN32-0BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON molded case circuit breaker, 3VA2063-6HN32-0BA0, 3-pole, 63 A rated current, 756 A frame, 242 kA breaking capacity at 240 V, with undervoltage release.","salesMarkdown":"The Siemens SENTRON 3VA2063-6HN32-0BA0 is a 3-pole molded case circuit breaker (MCCB) rated for 63 A continuous current across the full ambient range from 40 °C to 70 °C, with a 756 A frame that determines the maximum overcurrent trip setting. It carries an undervoltage release (UVR) as standard — a key detail for safety circuits where loss of control voltage must trip the breaker immediately. ## Breaking capacity at the voltages that matter At 240 V it interrupts 242 kA; at 415 V and 440 V it handles 187 kA; at 500 V the rating drops to 121 kA, and at 690 V it is still capable of 3 kA.","metaTitle":"Siemens 3VA2063-6HN32-0BA0 SENTRON MCCB, 63 A, 756 A, 242 kA","metaDescription":"Siemens SENTRON 3VA2063-6HN32-0BA0 molded case circuit breaker, 3-pole, 63 A rated, 756 A frame, 242 kA at 240 V. Undervoltage release included. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"756 A","Minimum":"756 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"7.9 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20636HN320AA0","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=440237&mlfb=3VA2063-6HN32-0BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2063-6HN32-0BA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2063-6HN32-0BA0?","answer":"This MCCB is sourced and quoted to order against an RFQ; availability and current pricing are confirmed at quote time."},{"question":"What is the depth of 3VA2063-6HN32-0BA0?","answer":"The depth is 86 mm (3.39 in)."},{"question":"What is the width of 3VA2063-6HN32-0BA0?","answer":"The width is 105 mm (4.13 in)."},{"question":"Will 3VA2063-6HN32-0BA0 drop into a panel specified around 3VA1110-5EF32-0LA0 without rewiring?","answer":"No — the 3VA2063 is a 63 A MCCB on a 756 A frame with an integral undervoltage release, while the 3VA1110 is a different frame size and rating; physical dimensions and terminal arrangements differ, so panel rework is required."},{"question":"What compliance documentation does this brand provide for 3VA2063-6HN32-0BA0?","answer":"Siemens SENTRON MCCBs typically carry UL, CSA, IEC, and CE certifications; specific declarations (RoHS, REACH) are available in the product documentation on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2063-6HN32-0BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2063-6HN32-0BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}