{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2063-6HN32-0HC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2063-6HN32-0HC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2063-6HN32-0HC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2063-6HN32-0HC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2063-6HN32-0HC0, molded case circuit breaker, 3-pole, 63 A, 242 kA at 240 V, line protection, ETU350 trip unit, shunt trip, 2 HQ auxiliary switches.","salesMarkdown":"## Siemens 3VA2063-6HN32-0HC0 — 63 A MCCB with ETU350, Shunt Trip, and 242 kA Breaking Capacity The Siemens 3VA2063-6HN32-0HC0 is a SENTRON molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 63 A at 40 °C through 50 °C, with a slight thermal derating curve above that — 60.6 A at 55 °C, 58.3 A at 60 °C, 55.9 A at 65 °C, and 53.6 A at 70 °C. Breaking capacity hits 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 4 kA at 690 V — this is a high-interrupting frame for high-fault utility or transformer-fed distribution. Rated insulation voltage Ui is 800 V, operating range -25 °C to 70 °C, storage -40 °C to 80 °C. Maximum power loss 5.4 W.","metaTitle":"Siemens 3VA2063-6HN32-0HC0 SENTRON MCCB, 63 A, 3-Pole, 242 k","metaDescription":"Siemens SENTRON 3VA2063-6HN32-0HC0 molded case circuit breaker, 63 A rated, 3-pole, 242 kA breaking at 240 V. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.6375 A","at 60 °C":"58.275 A","at 65 °C":"55.9125 A","at 70 °C":"53.55 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"5.4 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2063-6HN32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"756 A","Adjustable response value current / li min.":"756 A","Adjustable response value current / lr min.":"25 A","Adjustable response value current / Isd max.":"630 A","Adjustable response value current / Isd min.":"95 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=255912&mlfb=3VA2063-6HN32-0HC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2063-6HN32-0HC0/alternatives.json"},"ai":{"faq":[{"question":"What trip unit and accessories does 3VA2063-6HN32-0HC0 include?","answer":"ETU350 electronic overcurrent release, shunt trip (STL) for remote tripping, and two HQ auxiliary switches. No undervoltage release, no ground-fault monitoring, no communication module."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2063-6HN32-0HC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2063-6HN32-0HC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}