{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2063-6JP32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2063-6JP32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2063-6JP32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2063-6JP32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2063-6JP32-0AA0, 3-pole molded case circuit breaker, 63 A continuous, 242 kA breaking capacity at 240 V, ETU550 electronic trip unit, IP40 front protection.","salesMarkdown":"## What the 63 A continuous rating means for your panel The Siemens SENTRON 3VA2063-6JP32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 63 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. That 63 A holds flat at every 5 °C step in between, so it handles a warm enclosure without a current haircut. Breaking capacity is the real headline here: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V. The IP40 front protection means the front face is sealed against tools and wires over 1 mm, but the back and sides are open to the panel interior — standard for MCCBs mounted in a dead-front enclosure. The 105 mm width is the standard 4-module footprint for a 3-pole MCCB in the SENTRON 3VA frame — it occupies the same DIN-rail or mounting-plate slot as other 3VA breakers of this frame size. The ETU550 release includes a communication function, so it can report trip events and status over the integrated communication interface — useful for a centralized power-monitoring system without adding an external module. ## What trips people up on this part No undervoltage release and no voltage-trigger function are built in — if you need a shunt trip or UVR for emergency-off or undervoltage protection, that must be added as an external accessory. The trip indicator is also absent, so there is no mechanical flag on the front to show a trip event; the communication interface is the only way to remotely confirm a trip.","metaTitle":"3VA2063-6JP32-0AA0 SENTRON MCCB, 63 A, 242 kA at 240 V","metaDescription":"Siemens SENTRON 3VA2063-6JP32-0AA0 molded case circuit breaker, 63 A continuous, 242 kA breaking at 240 V, ETU550 release, IP40 front. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"756 A","Minimum":"95 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"5.4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 40% to 160%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=226595&mlfb=3VA2063-6JP32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2063-6JP32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Who supplies 3VA2063-6JP32-0AA0 and how is it quoted for volume purchases?","answer":"Sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is 3VA2063-6JP32-0AA0's listed depth?","answer":"86 mm (3.39 in)."},{"question":"What is 3VA2063-6JP32-0AA0's listed width?","answer":"105 mm (4.13 in)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2063-6JP32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2063-6JP32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}