{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2063-7HN32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2063-7HN32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2063-7HN32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2063-7HN32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2063-7HN32-0AA0, molded case circuit breaker, 3-pole, line protection, 63 A, ETU350 release, 330 kA at 240 V, IP40 front.","salesMarkdown":"The interrupting rating hits 330 kA at 240 V, 242 kA at 415 V, and 187 kA at 500 V, with a sharp drop to 3 kA at 690 V. That 330 kA figure at 240 V places it in the high-fault tier for industrial main or feeder duty where available short-circuit current is extreme. ## Ratings and release The overcurrent release is an ETU350 — an electronic trip unit with adjustable functions typical for selective coordination in industrial distribution. Power loss is a modest 3 W maximum. ## Integration dimensions The width is the critical fit dimension for multi-breaker panelboards — 105 mm is a standard 4-module footprint on most DIN-rail or busbar systems. Depth of 86 mm leaves clearance for rear-connected bus stabs or cable lugs in a typical 200 mm deep enclosure.","metaTitle":"Siemens 3VA2063-7HN32-0AA0 SENTRON MCCB, 63 A, 330 kA at 240","metaDescription":"Siemens SENTRON 3VA2063-7HN32-0AA0 molded case circuit breaker, 63 A continuous, 330 kA at 240 V interrupting rating. ETU350 release. Sourced to order. Request RFQ for price and av","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"3 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Courant permanent assigné Iu":"63 A","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"756 A","Adjustable response value current / li min.":"756 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Max. rated operational current of the frame size":"100 A","Mechanical Service Life (Switching Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/97ff40eafca01687580603353f5b933a.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=514932&mlfb=3VA2063-7HN32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2063-7HN32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2063-7HN32-0AA0?","answer":"The part is sourced and quoted to order against an RFQ. Submit a request for quote; current pricing and availability are confirmed at quote time through independent distribution channels."},{"question":"What is 3VA2063-7HN32-0AA0's listed depth?","answer":"The depth is 86 mm (3.39 in). That dimension is the front-to-back depth, measured from the mounting surface to the front of the breaker."},{"question":"What is 3VA2063-7HN32-0AA0's listed width?","answer":"The width is 105 mm (4.13 in). This is a 3-pole MCCB in a standard 105 mm wide housing, fitting typical panelboard cutouts and busbar systems."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2063-7HN32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2063-7HN32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}