{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-0HL32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-0HL32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-0HL32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-0HL32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-0HL32-0AA0, molded case circuit breaker, 3-pole, 100 A, 440 kA at 415 V AC, ETU320 electronic trip unit, IP40 front protection.","salesMarkdown":"The Siemens 3VA2110-0HL32-0AA0 is a SENTRON molded case circuit breaker rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling, which simplifies panel thermal budgeting in a crowded enclosure. Breaking capacity hits 440 kA at 415 V AC and 187 kA at 690 V AC, so this breaker handles high-fault scenarios common on large transformer secondaries or industrial mains without cascading upstream. The 3VA2110-0HL32-0AA0 measures 105 mm wide, 181 mm high, and 86 mm deep — it drops into standard SENTRON 3VA mounting footprints. Three-pole construction with no undervoltage release or shunt trip on this variant; the ETU320 handles all protection logic internally. Power loss is 7.7 W maximum at rated current — negligible for most enclosures but worth noting if you are packing multiple breakers into a sealed, non-ventilated cabinet.","metaTitle":"Siemens 3VA2110-0HL32-0AA0 SENTRON MCCB, 100A, 440kA at 415V","metaDescription":"Siemens 3VA2110-0HL32-0AA0 SENTRON molded case circuit breaker, 100A continuous, 440kA breaking at 415V AC. ETU320 trip unit, 3-pole, IP40 front. Active production. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 415 V":"440 kA","at 690 V":"187 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"7.7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"E","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1417385&mlfb=3VA2110-0HL32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-0HL32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for 3VA2110-0HL32-0AA0?","answer":"100 A continuous current, 440 kA breaking capacity at 415 V AC, 690 V AC rated operating voltage, 800 V rated insulation voltage. The ETU320 electronic trip unit provides adjustable protection curves."},{"question":"How do I get pricing and availability for 3VA2110-0HL32-0AA0?","answer":"Submit an RFQ through this listing. Pricing and stock levels are confirmed at quote time through independent distribution channels."},{"question":"What is the physical size of this MCCB?","answer":"105 mm wide, 181 mm high, 86 mm deep. It fits standard SENTRON 3VA panel cutouts."},{"question":"Does the 3VA2110-0HL32-0AA0 include ground-fault protection?","answer":"No, this variant ships without ground-fault monitoring. The ETU320 handles overcurrent protection only."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-0HL32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-0HL32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}