{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-0KP46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-0KP46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-0KP46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-0KP46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-0KP46-0AA0, molded case circuit breaker, 4-pole, 100 A continuous, ETU850 electronic trip unit, 440 kA breaking capacity at 415 V AC, line protection design.","salesMarkdown":"The Siemens SENTRON 3VA2110-0KP46-0AA0 is a 4-pole molded case circuit breaker rated 100 A continuous at 40 °C, with an ETU850 electronic trip unit that supports adjustable N-conductor protection (OFF, 20 % to 160 %). At 86 mm deep, 140 mm wide, and 181 mm tall, the 3VA2110-0KP46-0AA0 fits the standard SENTRON 3VA frame footprint. ## Trip unit and protection capabilities The N-conductor protection can be set from OFF to 20 %–160 % of the rated current, which is useful for systems with harmonic loads or unbalanced neutral currents. Rated insulation voltage is 800 V, and the breaker handles ambient temperatures from -25 °C to 70 °C, with no derating needed up to 70 °C (100 A continuous across the full range).","metaTitle":"Siemens 3VA2110-0KP46-0AA0 SENTRON MCCB, 100 A, ETU850, 440","metaDescription":"Siemens SENTRON 3VA2110-0KP46-0AA0 molded case circuit breaker, 100 A continuous, ETU850 electronic trip, 440 kA at 415 V AC. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 415 V":"440 kA","at 690 V":"187 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"5.51 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"7.7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"E","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1417400&mlfb=3VA2110-0KP46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-0KP46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2110-0KP46-0AA0?","answer":"Submit an RFQ through this listing. We source through multiple independent distribution channels and confirm current pricing and availability at quote time."},{"question":"What is 3VA2110-0KP46-0AA0's listed depth and width?","answer":"The depth is 86 mm and the width is 140 mm (4-pole)."},{"question":"Will 3VA2110-0KP46-0AA0 drop into a panel specified around 3VA2116-5JP32-0AE0 without rewiring?","answer":"Both breakers share the same SENTRON 3VA frame and 4-pole width, so the physical footprint and DIN-rail mounting are identical. However, the 3VA2116-5JP32-0AE0 has a different trip unit and current rating — verify the lug kit, busbar connections, and protection settings before swapping."},{"question":"What compliance documentation does Siemens provide for 3VA2110-0KP46-0AA0?","answer":"Siemens typically provides RoHS and REACH declarations, plus UL and IEC certification documentation for the SENTRON 3VA series. Specific certificates can be requested at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-0KP46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-0KP46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}