{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5HL32-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5HL32-0AB0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5HL32-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HL32-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker, 3VA2110-5HL32-0AB0, 100 A continuous, 3-pole, line protection, 187 kA breaking at 240 V.","salesMarkdown":"Its headline figure is 100 A continuous current, and it holds that rating across the full operating temperature range from 40 °C to 70 °C — no derating needed as the panel warms up, which simplifies panel design. The 3-pole construction handles three-phase circuits, and the insulation voltage is rated at 800 V, so it covers 400/480 V systems with headroom. At 240 V it interrupts 187 kA; at 415 V and 440 V it still handles 121 kA. At 690 V the rating drops to 3.7 kA, so it is not the right choice for 690 V distribution without coordination study. The adjustable overload range runs from 150 A to 1 200 A, which means the 100 A frame is actually a 100 A continuous breaker with a wide trip-setting window. That range covers motor feeders and general distribution where you need to dial in the exact protection point. The 3VA2110-5HL32-0AB0 measures 105 mm wide, 181 mm tall, and 86 mm deep — a standard MCCB footprint that fits most DIN-rail or panel-mount enclosures. The 86 mm depth is the dimension to check against gland-plate clearance or shallow backboxes; at 3.39 inches it usually clears a standard 200 mm enclosure depth. That keeps internal cabinet temperature rise manageable in a sealed enclosure, but if you stack several breakers in a small box, add up the dissipation and check the thermal rise.","metaTitle":"Siemens 3VA2110-5HL32-0AB0 SENTRON MCCB, 100 A, 3-Pole","metaDescription":"Siemens 3VA2110-5HL32-0AB0 SENTRON molded case circuit breaker, 100 A continuous, 3-pole, 187 kA at 240 V. Current lifecycle. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21105HL320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HP","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA11","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=72051&mlfb=3VA2110-5HL32-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HL32-0AB0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-5HL32-0AB0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 3VA2110-5HL32-0AB0 at 240 V?","answer":"At 240 V the breaking capacity is 187 kA. At 415 V and 440 V it is 121 kA."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5HL32-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5HL32-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}