{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5HL32-0AE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5HL32-0AE0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5HL32-0AE0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HL32-0AE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, molded case circuit breaker, order code 3VA2110-5HL32-0AE0, 100 A rated continuous current, 187 kA breaking capacity at 240 V AC, ETU320 electronic trip unit, 3-pole, IP40 front.","salesMarkdown":"## Breaking capacity — the real number for your fault study The 3VA2110-5HL32-0AE0: This breaker delivers 187 kA at 240 V AC, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V. At 415/440 V common in industrial plants, the 121 kA still gives you plenty of headroom for most distribution boards. The steep drop to 4.25 kA at 690 V means this isn't the right part for a 690 V main — you'd need a higher-rated frame for that. ## Thermal derating — don't cook it at 70 °C At 55 °C it derates to 96.25 A, at 60 °C to 92.5 A, at 65 °C to 88.75 A, and at 70 °C to 85 A. The 10 W maximum power loss also adds to the enclosure heat load; factor it into your thermal calculation. Footprint is 105 mm wide, 181 mm tall, 86 mm deep — standard SENTRON 3VA frame size for 100 A. IP40 on the front is fine for a dry indoor panel; don't use it in a washdown zone without an enclosure.","metaTitle":"Siemens 3VA2110-5HL32-0AE0 SENTRON MCCB, 100 A, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA2110-5HL32-0AE0 molded case circuit breaker, 100 A rated, 187 kA breaking at 240 V. ETU320 trip unit, 4 aux switches. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","title":"3VA2110-5HL32-0AE0","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"4.25 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","description":"circuit breaker 3VA2 IEC frame 160 breaking capacity class M Icu=55kA @ 415V 3-pole, line protection ETU320, LI, In=100A overload protection Ir=40A...100A short-circuit protection Ii=1.5...12 x In nut keeper kit 4 auxiliary switches HQ","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"10 W","Auxiliary contact version":"4 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-5HL32-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=29266&mlfb=3VA2110-5HL32-0AE0"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-5HL32-0AE0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."},{"question":"What are the key ratings of 3VA2110-5HL32-0AE0?","answer":"Rated 100 A continuous at 40 °C, 3-pole, with 187 kA breaking capacity at 240 V AC and 121 kA at 415 V. Uses an ETU320 electronic trip unit and includes four auxiliary switches."},{"question":"What is the panel footprint of this MCCB?","answer":"Width 105 mm, height 181 mm, depth 86 mm — standard SENTRON 3VA frame size for the 100 A rating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5HL32-0AE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5HL32-0AE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}