{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5HL32-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5HL32-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5HL32-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HL32-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-5HL32-0HA0, molded case circuit breaker, 3-pole, 100 A continuous rating, 187 kA breaking capacity at 240 VAC, line protection design with shunt trip release.","salesMarkdown":"The Siemens SENTRON 3VA2110-5HL32-0HA0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current, designed for line protection in distribution panels. The rated insulation voltage is 800 V, so it's comfortable on 480 V and 600 V class systems. This breaker delivers 187 kA at 240 VAC, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. The steep drop at 690 V tells you this is a 240–500 V class device; at 690 V the interrupting rating is low enough that you'd need a different frame for high-fault 690 V panels. For typical 480 V industrial distribution, 121 kA covers most high-fault scenarios without cascading upstream. ## Thermal performance — flat derating to 70 °C The continuous current rating holds at 100 A from 40 °C all the way to 70 °C — no derating curve to calculate. That's unusual for an MCCB; most frames start dropping at 50 °C. The 3VA2110-5HL32-0HA0 measures 181 mm high, 105 mm wide, and 86 mm deep. That 105 mm width is standard for a 3-pole SENTRON 3VA frame — it mounts on a DIN rail or bolts directly into the panel backplate.","metaTitle":"Siemens 3VA2110-5HL32-0HA0 SENTRON MCCB, 100 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2110-5HL32-0HA0 molded case circuit breaker, 100 A continuous, 3-pole, 187 kA breaking capacity at 240 VAC. Active production. Sourced to order; RFQ for current","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21105HL320AA0","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=470800&mlfb=3VA2110-5HL32-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HL32-0HA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2110-5HL32-0HA0?","answer":"Submit an RFQ through this listing. The part is sourced to order through independent distribution; pricing and stock are confirmed at quote time."},{"question":"What is the breaking capacity of 3VA2110-5HL32-0HA0 at 480 V?","answer":"At 440 V it's rated 121 kA, and at 500 V it's 75.6 kA. For a 480 V system, expect the 121 kA figure to apply — the datasheet interpolates between those two points."},{"question":"Does 3VA2110-5HL32-0HA0 include a shunt trip?","answer":"Yes, it's equipped with a shunt trip release (STL) for remote tripping via a control signal."},{"question":"What compliance documentation is available for this MCCB?","answer":"As a Siemens SENTRON product, it carries UL, CSA, and IEC certifications typical for the 3VA series. Specific RoHS and REACH declarations are available from Siemens on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5HL32-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5HL32-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}