{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5HL36-0AC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5HL36-0AC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5HL36-0AC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HL36-0AC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, molded case circuit breaker, 3VA2110-5HL36-0AC0, 3-pole, 100 A, 187 kA at 240 V AC, ETU320 electronic trip unit, IP40 front, depth 86 mm, width 105 mm, height 181 mm.","salesMarkdown":"The Siemens SENTRON 3VA2110-5HL36-0AC0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current at 40 °C, with a line-protection ETU320 electronic trip unit. Its interrupting capacity hits 187 kA at 240 V AC and 121 kA at 415 V AC — numbers that put it squarely in high-fault-duty panels where upstream SCCR headroom is critical. The 187 kA at 240 V AC and 121 kA at 415 V AC are the maximum fault currents this MCCB can safely interrupt without welding contacts or rupturing the case. That level of interrupting capacity is typical for main feeders in industrial switchboards where the available fault current from the transformer can exceed 100 kA. At 690 V the rating drops to 4.25 kA — still enough for most motor-circuit faults, but the real headroom lives at the lower voltages. The 100 A continuous rating holds flat from 40 °C to 50 °C (–). Above that, derating kicks in: 96.25 A at 55 °C, 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C. The MCCB measures 105 mm wide, 181 mm high, and 86 mm deep. The 2 HQ auxiliary switches provide status feedback for the PLC or HMI without a separate contactor block. That adjustability lets the panel designer achieve full selectivity with downstream 100 A or smaller breakers, so a fault on a branch doesn't take out the main feeder. The 800 V rated insulation voltage covers 480 V and 600 V class systems with margin.","metaTitle":"Siemens 3VA2110-5HL36-0AC0 SENTRON MCCB, 100 A, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA2110-5HL36-0AC0 molded case circuit breaker, 100 A rated current, 187 kA breaking capacity at 240 V AC. ETU320 electronic trip unit, 3-pole, IP40 front. Sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"4.25 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"10 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-5HL36-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=462508&mlfb=3VA2110-5HL36-0AC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HL36-0AC0/alternatives.json"},"ai":{"faq":[{"question":"Who supplies 3VA2110-5HL36-0AC0 and how is it quoted for volume purchases?","answer":"This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock count or price is listed here."},{"question":"What is 3VA2110-5HL36-0AC0's listed depth?","answer":"The depth is 86 mm."},{"question":"What is 3VA2110-5HL36-0AC0's listed width?","answer":"The width is 105 mm."},{"question":"Will 3VA2110-5HL36-0AC0 drop into a panel specified around 3VA1110-5EE32-0JA0 without rewiring?","answer":"The 3VA2110-5HL36-0AC0 is a higher-fault-duty variant (187 kA vs the 3VA1110's typical 65–100 kA range) and uses an ETU320 electronic trip unit versus the 3VA1110's thermal-magnetic or basic electronic trip. The mounting footprint and terminal spacing are similar across the 3VA family, so it will physically fit the same DIN-rail or backplate location, but the trip curve and settings differ — verify coordination with the existing downstream breakers before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5HL36-0AC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5HL36-0AC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}