{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5HL36-0AE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5HL36-0AE0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5HL36-0AE0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HL36-0AE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-5HL36-0AE0, molded case circuit breaker, 3-pole, 100A, ETU320 electronic trip, 187 kA at 240 V, 4 auxiliary switches HQ.","salesMarkdown":"No undervoltage release, no shunt trip, no ground-fault module — this is a straight line-protection breaker with the aux contacts factory-fitted. The breaker holds full 100 A up to 50 °C ambient; at 55 °C it derates to 96.25 A, at 60 °C to 92.5 A, at 65 °C to 88.75 A, and at 70 °C to 85 A. In a sealed enclosure or a hot machine cabinet, that derating curve tells you whether you need to step up to the next frame or add ventilation. The 105 mm width and 86 mm depth fit standard Siemens 3VA panel cutouts and busbar centers — no re-drilling if you're swapping a 3VA1 or earlier 3VL.","metaTitle":"Siemens 3VA2110-5HL36-0AE0 SENTRON MCCB, 100A, 187kA at 240V","metaDescription":"Siemens 3VA2110-5HL36-0AE0 SENTRON molded case circuit breaker, 3-pole, 100A, ETU320, 187kA at 240V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"4.25 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"10 W","Auxiliary contact version":"4 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-5HL36-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=357664&mlfb=3VA2110-5HL36-0AE0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HL36-0AE0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-5HL36-0AE0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing."},{"question":"What is 3VA2110-5HL36-0AE0's listed depth and width?","answer":"Depth is 86 mm; width is 105 mm. Height is 181 mm."},{"question":"Will 3VA2110-5HL36-0AE0 drop into a panel that was specified around 3VA1110-5EE32-0JA0 without rewiring?","answer":"Both are 3-pole SENTRON MCCBs on the same 105 mm width footprint, so the mechanical cutout and busbar centers are the same. However, the 3VA2110 carries an ETU320 electronic trip unit and 187 kA interrupting capacity, while the 3VA1110 uses a different trip system and lower breaking capacity — verify the trip curve and SCCR coordination before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5HL36-0AE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5HL36-0AE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}