{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5HL36-0AG0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5HL36-0AG0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5HL36-0AG0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HL36-0AG0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series molded case circuit breaker, 3VA2110-5HL36-0AG0, 3-pole, 100 A rated continuous current, ETU320 electronic trip unit, line protection version.","salesMarkdown":"The Siemens SENTRON 3VA2110-5HL36-0AG0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current at 40 °C, carrying the same 100 A rating through 50 °C before the thermal derating curve begins — at 55 °C it's 96.25 A, at 60 °C it's 92.5 A, and at 70 °C it's 85 A. That means for a panel sitting at 50 °C ambient (common in a crowded enclosure), you still get full 100 A without oversizing the frame. ## Sizing and integration into a DIN-rail enclosure Maximum power loss is 10 W, which is modest for a 100 A frame — keep that in mind for thermal calculations in a sealed enclosure. ## Sourcing this for a BOM line The 3VA2110-5HL36-0AG0 is specified into the BOM as a line-protection MCCB with the ETU320 release. For a panel originally built around the 3VA1010-2ED36-0AC0, this 3VA2110 frame is a different physical size and trip unit generation; it will not drop into the same cutout without panel modification. The 3VA2110 is the larger frame for higher interrupting capacity and the electronic trip option.","metaTitle":"Siemens SENTRON 3VA2110-5HL36-0AG0 MCCB, 100 A, 3-Pole, ETU3","metaDescription":"Siemens SENTRON 3VA2110-5HL36-0AG0 molded case circuit breaker, 100 A rated, 3-pole, line protection, ETU320 release. 187 kA at 240 V, 121 kA at 415 V. Current production. Quoted t","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"4.25 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"10 W","Auxiliary contact version":"1 auxiliary switch + 1 trip alarm switch HP","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-5HL36-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB11","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=375643&mlfb=3VA2110-5HL36-0AG0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HL36-0AG0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-5HL36-0AG0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"Will 3VA2110-5HL36-0AG0 drop into a panel specified around 3VA1010-2ED36-0AC0?","answer":"No. The 3VA2110 frame is physically larger (105 mm wide vs the 3VA1010's 70 mm frame) and uses a different trip unit generation. It will not fit the same cutout or busbar spacing without panel modification."},{"question":"What are the key interrupting ratings for 3VA2110-5HL36-0AG0?","answer":"At 240 V it interrupts 187 kA; at 415 V and 440 V it interrupts 121 kA; at 500 V it interrupts 79 kA; and at 690 V it interrupts 4.25 kA. The 100 A continuous rating holds through 50 °C ambient."},{"question":"What compliance documentation does Siemens provide for this MCCB?","answer":"The SENTRON 3VA series carries UL 489, IEC 60947-2, and CSA C22.2 No. 5 certifications. RoHS and REACH declarations are available from Siemens on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5HL36-0AG0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5HL36-0AG0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}