{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5HL36-0DL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5HL36-0DL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5HL36-0DL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HL36-0DL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-5HL36-0DL0, molded case circuit breaker, 3-pole, 100 A continuous, 187 kA at 240 V, line protection with undervoltage release.","salesMarkdown":"The Siemens SENTRON 3VA2110-5HL36-0DL0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. That flat thermal curve means it holds its 100 A rating in a warm panel without a size bump. Its interrupting ratings climb to 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. Verify the busbar or lug kit pattern against your existing panel layout; the basic switch variant is 3VA21105HL360AA0.","metaTitle":"Siemens 3VA2110-5HL36-0DL0 SENTRON MCCB, 100 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2110-5HL36-0DL0 molded case circuit breaker, 100 A continuous, 3-pole, 187 kA at 240 V. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"12.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21105HL360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=96100&mlfb=3VA2110-5HL36-0DL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HL36-0DL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-5HL36-0DL0?","answer":"The part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings of 3VA2110-5HL36-0DL0?","answer":"It is a 3-pole MCCB rated 100 A continuous (no derating up to 70 °C), with interrupting capacity of 187 kA at 240 V, 121 kA at 415 V, 121 kA at 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. It includes an undervoltage release and 2 auxiliary switches plus trip and electrical alarm switches."},{"question":"What compliance documentation does this brand provide for 3VA2110-5HL36-0DL0?","answer":"Siemens SENTRON breakers typically carry UL, CSA, CE, and IEC certifications; specific approval marks for this order code should be confirmed from the manufacturer's declaration at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5HL36-0DL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5HL36-0DL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}