{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5HL36-0JL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5HL36-0JL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5HL36-0JL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HL36-0JL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON, molded case circuit breaker, 3VA2110-5HL36-0JL0, 3-pole, 100 A continuous, adjustable thermal-magnetic trip 150–1200 A, 187 kA at 240 V, line protection with shunt trip and auxiliary switches.","salesMarkdown":"Three-pole construction, designed for line protection (cable/feeder protection, not motor-only duty). The adjustable thermal-magnetic trip unit spans 150 A minimum to 1 200 A maximum — that's a wide magnetic pickup window, so you set the instantaneous trip threshold to coordinate with downstream branch breakers without nuisance tripping on inrush. Breaking capacity is voltage-dependent: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. At 415 V — common in European industrial distribution — the 121 kA rating handles high-fault scenarios like transformer secondaries or busway taps without cascading upstream. Maximum power loss is 10 W. In a sealed, non-ventilated enclosure, that 10 W contributes to internal temperature rise; factor it into the thermal calculation if the panel also houses drives or transformers. ## Auxiliary hardware onboard The auxiliary switches signal breaker position to a PLC or status lamp; the alarm switches indicate a trip event separately from normal open/close. No undervoltage release fitted — if undervoltage protection is needed, that's a separate order. The voltage trigger allows a remote signal to initiate a trip — useful in emergency-stop circuits where a safety relay cuts power via the shunt trip rather than dropping out a contactor.","metaTitle":"Siemens 3VA2110-5HL36-0JL0 SENTRON MCCB, 100 A, 3-Pole, 150-","metaDescription":"Siemens 3VA2110-5HL36-0JL0 SENTRON molded case circuit breaker, 100 A continuous, 3-pole, adjustable thermal-magnetic trip 150-1200 A, 187 kA at 240 V. Current production. Quoted o","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21105HL360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=375856&mlfb=3VA2110-5HL36-0JL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HL36-0JL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-5HL36-0JL0 and get a price?","answer":"This part is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."},{"question":"What is the depth of 3VA2110-5HL36-0JL0?","answer":"86 mm (3.39 in) deep, with a width of 105 mm and height of 181 mm."},{"question":"What is the continuous current rating of 3VA2110-5HL36-0JL0?","answer":"100 A continuous, and that rating holds from 40 °C through 70 °C ambient without derating."},{"question":"Does 3VA2110-5HL36-0JL0 include a shunt trip?","answer":"Yes, it ships with a shunt trip (STL) release, two auxiliary switches, one trip alarm switch, and one electrical alarm switch (HQ)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5HL36-0JL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5HL36-0JL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}