{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5HL36-0KL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5HL36-0KL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5HL36-0KL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HL36-0KL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-5HL36-0KL0, molded case circuit breaker, 3-pole, 100 A continuous, trip range 150–1200 A, interrupting capacity 187 kA at 240 V, 121 kA at 415/440 V.","salesMarkdown":"The Siemens SENTRON 3VA2110-5HL36-0KL0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current across the full -25 °C to 70 °C operating range — no derating needed up to 70 °C ambient. Its electronic trip unit adjusts between 150 A and 1200 A, covering line-feeder and distribution protection in industrial panels. Interrupting capacity is voltage-dependent: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. That 187 kA figure at 240 V gives substantial headroom for high-fault panels — useful where the available fault current approaches 200 kA. ## Physical integration and auxiliary configuration Dimensions are 105 mm wide, 181 mm tall, and 86 mm deep — a standard 3-pole MCCB footprint for panel-mounting on a backplate or DIN rail adapter. Factory-fitted auxiliaries include 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ type), plus a shunt trip (STL) release. Maximum power loss is 10 W. ## What the interrupting ratings mean for selectivity The 121 kA rating at 415 V and 440 V covers most European and Asian industrial distribution panels. At 690 V the rating drops to 3.7 kA — this breaker is not intended for primary 690 V feeders with high fault current; it is a line-protection device for standard low-voltage networks.","metaTitle":"Siemens 3VA2110-5HL36-0KL0 SENTRON MCCB, 100 A, 150–1200 A t","metaDescription":"Siemens SENTRON 3VA2110-5HL36-0KL0 molded case circuit breaker, 100 A continuous, 150–1200 A trip range, 187 kA at 240 V. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21105HL360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=283578&mlfb=3VA2110-5HL36-0KL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HL36-0KL0/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source for 3VA2110-5HL36-0KL0?","answer":"The peer order codes 3VA1110-5EF32-0AM0 and 3VA1110-5ED36-0AA0 are in the same SENTRON family but carry different trip-unit configurations and auxiliary layouts. The 3VA2110-5HL36-0KL0 is the line-protection variant with the full auxiliary switch set (2 aux + trip alarm + electrical alarm) and shunt trip — verify the specific trip range and aux count before substituting."},{"question":"Will 3VA2110-5HL36-0KL0 drop into a panel specified around 3VA1110-5EF32-0AM0?","answer":"Both are 3-pole SENTRON MCCBs with the same basic frame dimensions, so the physical footprint is compatible. However, the auxiliary switch configuration and trip unit differ — the 3VA2110-5HL36-0KL0 carries 2 aux switches plus trip and electrical alarm switches, plus a shunt trip, which may require different wiring or panel layout. Verify the aux contact count and release type against your panel schematic before drop-in replacement."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5HL36-0KL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5HL36-0KL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}