{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5HN32-0AC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5HN32-0AC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5HN32-0AC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HN32-0AC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker, 3-pole, 100 A rated continuous current, ETU350 electronic trip unit, breaking capacity 187 kA at 240 V AC.","salesMarkdown":"The 3VA2110-5HN32-0AC0: Thermal derating is published per the datasheet: the breaker carries 100 A continuously up to 50 °C ambient, then derates to 96.25 A at 55 °C, 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C. IP40 on the front face, meaning protection against solid objects over 1 mm but no water ingress protection; this is a panel-interior device, not a washdown or outdoor unit. The auxiliary contact version is 2 auxiliary switches HQ, which provide status feedback for the open/closed position and the trip condition — useful for PLC inputs or remote indication.","metaTitle":"Siemens 3VA2110-5HN32-0AC0 SENTRON MCCB, 100 A, 187 kA at 24","metaDescription":"Siemens 3VA2110-5HN32-0AC0 SENTRON molded case circuit breaker, 3-pole, 100 A rated, ETU350 trip unit, breaking capacity 187 kA at 240 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"4.25 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"10 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-5HN32-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"1 200 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"150 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=298775&mlfb=3VA2110-5HN32-0AC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HN32-0AC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-5HN32-0AC0 and get a price?","answer":"This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — figures are confirmed at quote time and vary with market conditions."},{"question":"What is the breaking capacity of 3VA2110-5HN32-0AC0 at different voltages?","answer":"187 kA at 240 V AC, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V. The 121 kA at 415 V is the figure that governs most 400 V distribution panels."},{"question":"What are the physical dimensions of 3VA2110-5HN32-0AC0?","answer":"Width 105 mm, height 181 mm, depth 86 mm. The 86 mm depth is from the mounting surface to the front of the breaker."},{"question":"Does 3VA2110-5HN32-0AC0 drop into a panel specified around 3VA1110-5EE32-0JA0?","answer":"Both are 3-pole SENTRON MCCBs with similar frame sizes, but the 3VA2110-5HN32-0AC0 carries an ETU350 electronic trip unit versus the 3VA1110-5EE32-0JA0's trip configuration. Physical footprint and mounting pattern are the same, but the trip curve and coordination study must be verified — the electronic trip unit changes the protection profile."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5HN32-0AC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5HN32-0AC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}