{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5HN36-0DH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5HN36-0DH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5HN36-0DH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HN36-0DH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-5HN36-0DH0, molded case circuit breaker, 3-pole, 100 A, 187 kA at 240 V, line protection, with undervoltage release.","salesMarkdown":"The Siemens SENTRON 3VA2110-5HN36-0DH0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current across the full ambient temperature range from 40 °C to 70 °C — no derating needed as the temperature climbs. This MCCB carries a 187 kA interrupting rating at 240 V, dropping to 121 kA at 415 V and 440 V, then 75.6 kA at 500 V, and 3.7 kA at 690 V. The steep drop at 690 V (3.7 kA) means this breaker is not intended for 690 V main feeders; it's a 480 V / 600 V class device. ## Built-in undervoltage release and auxiliary switching The UVR and auxiliary switch complement is built into the basic switch assembly (3VA21105HN360AA0), not field-added. ## Physical fit: panel dimensions and integration That 105 mm width (about 4.13 in) is standard for a 3-pole MCCB in this frame size — it occupies three 35 mm DIN module widths plus a bit.","metaTitle":"Siemens 3VA2110-5HN36-0DH0 SENTRON MCCB, 100 A, 3-Pole","metaDescription":"Siemens SENTRON 3VA2110-5HN36-0DH0 molded case circuit breaker, 100 A continuous, 3-pole, 187 kA at 240 V. Line protection with undervoltage release. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"12.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21105HN360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=197390&mlfb=3VA2110-5HN36-0DH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HN36-0DH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-5HN36-0DH0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."},{"question":"What is the closest functional second-source for 3VA2110-5HN36-0DH0?","answer":"The 3VA1110-5EF32-0AM0 is a different frame variant in the same SENTRON 3VA family, but it does not carry the same undervoltage release or auxiliary switch configuration. Panel rewiring would be required if swapping between them — the auxiliary contacts and release options differ."},{"question":"Will 3VA2110-5HN36-0DH0 drop into a panel specified around 3VA1110-5EF32-0AM0?","answer":"Not without rewiring. The 3VA2110-5HN36-0DH0 has a factory-fitted undervoltage release and two auxiliary switches plus a trip alarm, while the 3VA1110-5EF32-0AM0 has a different auxiliary and release configuration. The physical footprint is similar, but control wiring differs."},{"question":"What compliance documentation does Siemens provide for 3VA2110-5HN36-0DH0?","answer":"As a standard SENTRON MCCB, it carries CE marking for the European market and is designed to meet IEC 60947-2. UL and CSA listings are typical for the 3VA series, but specific certification for this exact order code should be confirmed against the nameplate or Siemens documentation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5HN36-0DH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5HN36-0DH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}