{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5HN36-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5HN36-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5HN36-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HN36-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-5HN36-0JH0, molded case circuit breaker, 3-pole, 100 A rated current, 187 kA breaking capacity at 240 V, line protection design.","salesMarkdown":"The Siemens SENTRON 3VA2110-5HN36-0JH0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed in a warm panel. The interrupting ratings are substantial: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. The 3VA2110-5HN36-0JH0 measures 105 mm wide by 181 mm tall by 86 mm deep — a standard 4.13 in × 7.13 in × 3.39 in footprint that fits common MCCB panel cutouts. That alarm switch gives a positive signal when the breaker trips on fault, which is useful for remote annunciation or PLC input. The undervoltage release is not fitted, so if you need UVR protection you'll order a different variant or add it separately.","metaTitle":"Siemens SENTRON 3VA2110-5HN36-0JH0 MCCB, 100 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2110-5HN36-0JH0 molded case circuit breaker, 100 A continuous, 3-pole, 187 kA at 240 V. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21105HN360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=536481&mlfb=3VA2110-5HN36-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5HN36-0JH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-5HN36-0JH0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or price figures are published here."},{"question":"What are the key ratings for 3VA2110-5HN36-0JH0?","answer":"It is a 3-pole MCCB rated 100 A continuous from 40 °C to 70 °C, with interrupting capacity of 187 kA at 240 V, 121 kA at 415 V, and 3.7 kA at 690 V. It measures 105 mm wide by 181 mm tall by 86 mm deep."},{"question":"Will 3VA2110-5HN36-0JH0 drop into a panel specified for 3VA2116-5HL32-0AK0?","answer":"The 3VA2110-5HN36-0JH0 is a 100 A frame; the 3VA2116-5HL32-0AK0 is a different rating. Both are 3-pole SENTRON MCCBs in the same physical platform, so the mounting footprint and bus connections are identical — no rewiring needed for the panel cutout. Confirm the load current and protection settings before substitution."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5HN36-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5HN36-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}