{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5JP32-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5JP32-0AB0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5JP32-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5JP32-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series molded case circuit breaker, 3-pole, 100 A, ETU550 electronic trip unit, line protection, 187 kA at 240 V, IP40 front.","salesMarkdown":"The ETU550 electronic trip unit handles the overcurrent release — that's the brain that decides when to clear a fault. This is a communicating breaker; it has a communication function on board, so it can talk to a higher-level control system for monitoring and coordination. The interrupting ratings tell you what faults this breaker can safely clear at different voltages: 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V. At 690 V the number drops sharply — that's the physics of arc extinction in air. If your system fault current at 690 V exceeds 4.25 kA, this breaker isn't your choice; you'd need a higher-rated frame. The continuous current holds at 100 A from 40 °C through 50 °C ambient, then derates to 96.25 A at 55 °C, 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C. The auxiliary contact version ships with 2 auxiliary switches HP built in, so you get remote status without adding a separate module. The SENTRON 3VA series carries the usual suite of compliance docs: RoHS, REACH, and the CE marking for the European market. UL and IEC certifications are standard for this product class. Documentation — datasheet, manual, CAD files — is available from Siemens on request.","metaTitle":"Siemens 3VA2110-5JP32-0AB0 SENTRON MCCB, 100 A, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA2110-5JP32-0AB0 molded case circuit breaker. 3-pole, 100 A, ETU550 release. SCCR 187 kA at 240 V. Current production. Sourced to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"4.25 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"10 W","Auxiliary contact version":"2 auxiliary switches HP","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-5JP32-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU550","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"25","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"60 A","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA11","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Mechanical service life (switching cycles) / typical":"20 000","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=384076&mlfb=3VA2110-5JP32-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5JP32-0AB0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5JP32-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5JP32-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}