{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5JP32-0DC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5JP32-0DC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5JP32-0DC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5JP32-0DC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-5JP32-0DC0, molded case circuit breaker, 3-pole, 100 A continuous, 150–1 200 A adjustable trip, line protection design, undervoltage release, 2 HQ auxiliary switches, communication capable.","salesMarkdown":"The Siemens 3VA2110-5JP32-0DC0 is a SENTRON molded case circuit breaker rated for 100 A continuous current with an adjustable thermal-magnetic trip range from 150 A minimum to 1 200 A maximum — meaning you set the pickup to match the load, not the other way around. It is a 3-pole unit built for line protection, so it sits at the feeder or branch in a distribution panel, not on a motor starter. The interrupting ratings are the headline: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. Thermal performance is flat across the board: 100 A at 40 °C, 45 °C, 50 °C, 55 °C, 60 °C, 65 °C, and 70 °C. No derating curve to calculate — if the ambient inside the panel hits 70 °C, this breaker still holds its full 100 A rating. That saves you a frame size upgrade in a hot enclosure. The two HQ aux switches give you status feedback (open/closed/tripped) for the PLC or annunciator without adding external relays. It also carries a communication function, so it can talk to a higher-level system for metering or remote trip indication — useful in a monitored distribution panel where you want to know which breaker opened before you walk the floor. ## Panel fit and environmental range The storage limit is the handling limit — if it sat in an unheated warehouse at -40 °C, it's fine once it warms up before energizing. For a BOM freeze or a panel that was specified around the 3VA1110-5EF32-0AM0, this 3VA2110-5JP32-0DC0 is a different frame and trip range — the 3VA1110 is a 160 A frame, this is a 1 200 A frame. They are not drop-in interchangeable; check the panel cutout and bus bar spacing before substituting.","metaTitle":"Siemens 3VA2110-5JP32-0DC0 SENTRON MCCB, 100A, 150-1200A Tri","metaDescription":"Siemens 3VA2110-5JP32-0DC0 SENTRON molded case circuit breaker, 100A continuous, 150-1200A trip range, 187kA at 240V. Active production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"12.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21105JP320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=264697&mlfb=3VA2110-5JP32-0DC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5JP32-0DC0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting rating of 3VA2110-5JP32-0DC0 at 240 V?","answer":"187 kA at 240 V, which is the highest interrupting rating on this breaker — suitable for high-fault-capacity service entrance or transformer secondary applications."},{"question":"Does 3VA2110-5JP32-0DC0 require derating at high ambient temperatures?","answer":"No derating needed up to 70 °C — it holds 100 A continuous from 40 °C through 70 °C."},{"question":"What auxiliaries come with 3VA2110-5JP32-0DC0?","answer":"It includes an undervoltage release and two HQ auxiliary switches for status feedback."},{"question":"Where can I buy 3VA2110-5JP32-0DC0 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"Will 3VA2110-5JP32-0DC0 drop into a panel specified for 3VA1110-5EF32-0AM0?","answer":"No — the 3VA2110 is a 1 200 A frame versus the 3VA1110's 160 A frame. Different footprint and bus bar spacing; verify panel cutout dimensions before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5JP32-0DC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5JP32-0DC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}