{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5JP32-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5JP32-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5JP32-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5JP32-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-5JP32-0JA0, molded case circuit breaker, 3-pole, 100 A continuous, line protection, with shunt trip and communication function.","salesMarkdown":"It carries a shunt trip release (STL) and a communication function, meaning it can be remotely tripped and integrated into a monitoring network — useful when you need to kill a feeder from a PLC or SCADA without walking the panel. ## Interrupting capacity and thermal performance At 240 V it interrupts 187 kA; at 415 V and 440 V that drops to 121 kA, then 75.6 kA at 500 V, and 3.7 kA at 690 V. No trip indicator on the front face, so fault status comes from the communication function or a visual check of the handle position.","metaTitle":"Siemens 3VA2110-5JP32-0JA0 SENTRON MCCB, 100 A, 3-Pole","metaDescription":"Siemens 3VA2110-5JP32-0JA0 SENTRON 3-pole MCCB, 100 A continuous, 187 kA at 240 V, 121 kA at 415 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21105JP320AA0","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=442940&mlfb=3VA2110-5JP32-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5JP32-0JA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get pricing and availability for 3VA2110-5JP32-0JA0?","answer":"Submit an RFQ through this listing. The part is sourced to order through independent distribution; current pricing and stock position are confirmed at quote time."},{"question":"What is the interrupting capacity of 3VA2110-5JP32-0JA0 at 415 V?","answer":"It interrupts 121 kA at 415 V, and the same 121 kA at 440 V."},{"question":"Will 3VA2110-5JP32-0JA0 drop into a panel specified for 3VA2116-5JP32-0AE0?","answer":"Both are 3-pole SENTRON MCCBs with the same 105 mm width and DIN-rail mounting. The 3VA2116 is a higher-current frame (160 A continuous versus 100 A), so the 3VA2110 fits the same footprint but serves a lower ampacity feeder."},{"question":"Does this breaker require derating in a hot panel?","answer":"No derating needed. The 100 A rating holds steady from 40 °C through 70 °C ambient."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5JP32-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5JP32-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}