{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5JQ32-0CC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5JQ32-0CC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5JQ32-0CC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5JQ32-0CC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, molded case circuit breaker, 3VA2110-5JQ32-0CC0, 3-pole, 100 A, interrupting 187 kA at 240 V, line protection with ETU560 electronic trip unit.","salesMarkdown":"## What this 3VA2110-5JQ32-0CC0 does on the line Its rated continuous current Iu is 100 A, and it carries a full-rated current up to 50 °C — at 55 °C it derates to 96.25 A, at 60 °C to 92.5 A, at 65 °C to 88.75 A, and at 70 °C to 85 A. The interrupting ratings are where this breaker earns its panel space: 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V. The integrated undervoltage release (UVR) and the two HQ auxiliary switches provide control interface for safety circuits and status feedback. It includes a communication function — for PROFIBUS or PROFINET via the 3VA communication modules — so it fits into a digital switchgear scheme where you want trip data and remote operation. ## Panel fit and physical constraints The trip indicator is not present on this variant, so fault status relies on the auxiliary switches or the communication interface.","metaTitle":"Siemens 3VA2110-5JQ32-0CC0 SENTRON MCCB, 100 A, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA2110-5JQ32-0CC0 molded case circuit breaker, 3-pole, 100 A, 187 kA interrupting at 240 V. Line protection with ETU560. Current lifecycle. Available to order, pri","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"4.25 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"12.5 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-5JQ32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Summation current formation L-conductor","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"ETU560","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"25","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / lg max.":"100 A","Adjustable response value current / lg min.":"20 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"60 A","Ground fault protection can be switched ON/OFF":"Yes","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSIG","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=141371&mlfb=3VA2110-5JQ32-0CC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5JQ32-0CC0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5JQ32-0CC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5JQ32-0CC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}