{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5JQ32-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5JQ32-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5JQ32-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5JQ32-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, molded case circuit breaker, 3VA2110-5JQ32-0JA0, 3-pole, 100 A rated continuous current, 187 kA breaking capacity at 240 V, ETU560 electronic trip unit, shunt trip release, communication function.","salesMarkdown":"Its interrupting capacity hits 187 kA at 240 V, dropping to 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V — so the 240 V figure is the headline, but the 415 V and 440 V numbers are what matter for most industrial 400 V-class distribution panels. ## Thermal derating — the real continuous current At 55 °C it derates to 96.25 A, at 60 °C to 92.5 A, at 65 °C to 88.75 A, and at 70 °C to 85 A. ## Footprint and panel fit Dimensions are 105 mm wide, 181 mm high, 86 mm deep — a standard SENTRON 3VA frame size for a 100 A, 3-pole MCCB.","metaTitle":"Siemens 3VA2110-5JQ32-0JA0 SENTRON MCCB, 100 A, 187 kA","metaDescription":"Siemens SENTRON 3VA2110-5JQ32-0JA0 molded case circuit breaker, 100 A rated continuous current, 187 kA at 240 V. ETU560 release, shunt trip, communication-ready. Current production","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"4.25 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"10 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-5JQ32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Summation current formation L-conductor","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU560","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"25","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / lg max.":"100 A","Adjustable response value current / lg min.":"20 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"60 A","Ground fault protection can be switched ON/OFF":"Yes","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSIG","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=270897&mlfb=3VA2110-5JQ32-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5JQ32-0JA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-5JQ32-0JA0 and get a price?","answer":"It is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."},{"question":"What is the breaking capacity of this MCCB at 240 V?","answer":"187 kA at 240 V. At 415 V and 440 V it is 121 kA, at 500 V it is 79 kA, and at 690 V it is 4.25 kA."},{"question":"Will 3VA2110-5JQ32-0JA0 drop into a panel specified around 3VA1110-5EE32-0JA0?","answer":"The 3VA2110 frame is physically larger than the 3VA1110 frame — 105 mm wide versus the 3VA1110's narrower footprint. It will not drop into the same mounting cutout or DIN-rail position without panel modification. Check the panel's spare width and bus-bar tap spacing before ordering."},{"question":"What compliance documentation is available for this part?","answer":"As a current-production SENTRON MCCB, it carries the standard Siemens declarations — RoHS, REACH, and CE marking for the EU market. UL and IEC listings are typical for the 3VA series; verify the specific certification for your jurisdiction at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5JQ32-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5JQ32-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}