{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5JQ32-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5JQ32-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5JQ32-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5JQ32-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-5JQ32-0JC0, molded case circuit breaker, 3-pole, 100 A rated continuous current, ETU560 electronic trip unit, line protection version, 86 mm depth × 105 mm width × 181 mm height.","salesMarkdown":"Breaking capacity varies with system voltage: 187 kA at 240 V, 121 kA at both 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V. These are the values for the 3VA2110-5JQ32-0JC0 per the datasheet — the 4.25 kA figure at 690 V is the limit that governs any 690 V application, not a higher value from a different variant. For selectivity coordination studies, use these published figures rather than a generic family curve. At 55 °C it derates to 96.25 A, at 60 °C to 92.5 A, at 65 °C to 88.75 A, and at 70 °C to 85 A. Maximum power loss is 10 W. ## Mounting and enclosure fit Dimensions are 86 mm depth, 105 mm width, 181 mm height. ## Trip unit and auxiliary configuration The ETU560 electronic trip unit supports adjustable overload and short-circuit protection settings. Latching endurance is 20,000 cycles.","metaTitle":"Siemens 3VA2110-5JQ32-0JC0 SENTRON MCCB, 100A, 3-Pole, ETU56","metaDescription":"Siemens SENTRON 3VA2110-5JQ32-0JC0 molded case circuit breaker, 100A rated, 3-pole, ETU560 trip unit. Breaking capacity 187kA at 240V. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"4.25 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"10 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-5JQ32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Summation current formation L-conductor","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU560","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"25","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / lg max.":"100 A","Adjustable response value current / lg min.":"20 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"60 A","Ground fault protection can be switched ON/OFF":"Yes","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSIG","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=516512&mlfb=3VA2110-5JQ32-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5JQ32-0JC0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5JQ32-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5JQ32-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}