{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5KP32-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5KP32-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5KP32-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5KP32-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-5KP32-0HA0, molded case circuit breaker, 3-pole, 100 A continuous, 187 kA breaking at 240 V, line protection with shunt trip and communication.","salesMarkdown":"The Siemens SENTRON 3VA2110-5KP32-0HA0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. At 240 V the breaker interrupts 187 kA — enough for high-fault service-entrance panels. At 415 V and 440 V it holds 121 kA, dropping to 75.6 kA at 500 V and 3.7 kA at 690 V. The shunt trip release allows remote tripping from a safety circuit or emergency-stop chain. Communication function supports integration into a higher-level monitoring system, though the specific protocol is not listed here.","metaTitle":"Siemens 3VA2110-5KP32-0HA0 SENTRON MCCB, 100 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2110-5KP32-0HA0 molded case circuit breaker, rated 100 A continuous, 3-pole, 187 kA breaking at 240 V. Active production, quoted to order. RFQ for volume.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Of The Supplied Basic Switch":"3VA21105KP320AA0","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=140601&mlfb=3VA2110-5KP32-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5KP32-0HA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2110-5KP32-0HA0 at 415 V?","answer":"At 415 V the breaker interrupts 121 kA."},{"question":"What is the continuous current rating of 3VA2110-5KP32-0HA0?","answer":"The continuous current rating is 100 A, and it holds that rating without derating from 40 °C up to 70 °C ambient."},{"question":"Where can I buy 3VA2110-5KP32-0HA0 and how is it quoted?","answer":"The breaker is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5KP32-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5KP32-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}