{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5KP32-0HL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5KP32-0HL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5KP32-0HL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5KP32-0HL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-5KP32-0HL0, Molded case circuit breaker, 3-pole, 100 A, line protection, 187 kA at 240 V, 86 mm depth, 105 mm width, 181 mm height.","salesMarkdown":"It carries a breaking capacity of 187 kA at 240 V AC, tapering to 121 kA at 415/440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V — figures that define its fault-interruption capability across common industrial voltages. The 187 kA at 240 V is the highest interrupting rating on this frame; at 690 V the same breaker interrupts 3.7 kA, so verify the available fault current at your system voltage. The 10 W maximum power loss is modest for a 100 A frame, keeping heat buildup manageable in a crowded DIN-rail or panel-mount arrangement. The 105 mm width for a 3-pole 100 A frame is standard for SENTRON 3VA2 breakers — it fits the same mounting footprint as other 3VA2 three-pole units, so a panel laid out for a 3VA2116-5JP32-0AE0 will accept this breaker without rewiring, provided the continuous current and trip characteristics match the application.","metaTitle":"Siemens 3VA2110-5KP32-0HL0 SENTRON MCCB, 100 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2110-5KP32-0HL0 molded case circuit breaker, 100 A continuous, 3-pole, line protection. Breaking capacity 187 kA at 240 V. Current production. Available to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Of The Supplied Basic Switch":"3VA21105KP320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=96962&mlfb=3VA2110-5KP32-0HL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5KP32-0HL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-5KP32-0HL0 and what is the lead time?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead-time estimate."},{"question":"Will 3VA2110-5KP32-0HL0 drop into a panel specified for 3VA2116-5JP32-0AE0?","answer":"Yes — both are 3-pole SENTRON 3VA2 breakers with the same 105 mm width and 181 mm height, so the mounting footprint and bus-bar spacing are identical. Verify that the 100 A continuous rating and the trip curve of the 3VA2110-5KP32-0HL0 meet your load requirements before substituting."},{"question":"What compliance documentation is available for this MCCB?","answer":"As a Siemens SENTRON product, the 3VA2110-5KP32-0HL0 is manufactured to IEC 60947-2 and typically carries CE, UL, and CSA certifications. RoHS and REACH declarations are standard from Siemens for this series. Specific certificate numbers should be confirmed from the manufacturer's documentation portal or requested at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5KP32-0HL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5KP32-0HL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}