{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5MN32-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5MN32-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5MN32-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5MN32-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker, 3VA2110-5MN32-0DA0, 100 A, 3-pole, motor protection design, 187 kA at 240 V breaking capacity, undervoltage release.","salesMarkdown":"Three poles, motor protection design with integrated phase failure detection and an undervoltage release (UVR) built in. That UVR means the breaker trips if control voltage drops, which is standard for motor starter feeder circuits where loss of control power should drop the load. Breaking capacity hits 187 kA at 240 V, 121 kA at 415/440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. The 3.7 kA at 690 V tells you this is a 600 V class frame, not a full 690 V performer; at that voltage the breaker is basically a disconnect, not a fault-interrupting device. That 105 mm width is a three-pole frame — fits standard panel cutouts for 100 A MCCBs. This is a straight motor-protection breaker with undervoltage release; if you need remote trip indication or GF protection, you step up to a different 3VA2 variant. The undervoltage release coil needs a separate control power feed; verify polarity on the UVR terminals if using DC control voltage. Phase failure detection is internal, no extra module required.","metaTitle":"Siemens 3VA2110-5MN32-0DA0 SENTRON MCCB, 100 A, 3-Pole, Moto","metaDescription":"Siemens 3VA2110-5MN32-0DA0 SENTRON molded case circuit breaker, 100 A continuous, 3-pole, motor protection design with undervoltage release. 187 kA at 240 V. Current production. So","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"17 s","Minimum":"4 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"12.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21105MN320AA0","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"30 000 W","operating power / at AC-3 / at 400 V":"55 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"E","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569351&mlfb=3VA2110-5MN32-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5MN32-0DA0/alternatives.json"},"ai":{"faq":[{"question":"Does 3VA2110-5MN32-0DA0 include undervoltage release?","answer":"Yes, it includes an undervoltage release (UVR) as the auxiliary release type. The breaker trips when control voltage drops below the dropout threshold."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5MN32-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5MN32-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}