{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5MN32-0DL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5MN32-0DL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5MN32-0DL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5MN32-0DL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-5MN32-0DL0, molded case circuit breaker, 3-pole, 100 A, motor protection design with undervoltage release, phase failure detection, 187 kA breaking capacity at 240 V.","salesMarkdown":"## MCCB for Motor Protection with Full Breaking Capacity Coverage The Siemens SENTRON 3VA2110-5MN32-0DL0 is a 3-pole molded case circuit breaker (MCCB) rated at 100 A across the full ambient temperature range from 40 °C to 70 °C — no derating needed up to that ceiling. The interrupting ratings climb to 187 kA at 240 V and hold at 121 kA through 415–440 V; at 500 V it still clears 75.6 kA, and even at 690 V it manages 3.7 kA — a curve that covers most industrial distribution voltages without a series-rated upstream breaker. The auxiliary switch complement includes two auxiliary switches plus a trip alarm and an electrical alarm switch, giving the PLC or BMS a dedicated fault signal path independent of the undervoltage release circuit. A visible trip indicator confirms the breaker state at the panel door without needing to open the cover — useful for concurrent-maintenance walkthroughs where every second of fault isolation counts. This order code carries a current-production lifecycle stage, so it remains an active BOM line for new panel builds and spares planning. The 12.5 W maximum power loss is modest for a 100 A frame, keeping enclosure heat rise manageable in a packed cabinet.","metaTitle":"Siemens 3VA2110-5MN32-0DL0 SENTRON MCCB, 100 A, 3-Pole, Moto","metaDescription":"Siemens 3VA2110-5MN32-0DL0 SENTRON molded case circuit breaker, 100 A rated at 40°C, 3-pole, motor protection design with phase failure detection and undervoltage release. Breaking","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"17 s","Minimum":"4 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"12.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21105MN320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"30 000 W","operating power / at AC-3 / at 400 V":"55 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"E","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569354&mlfb=3VA2110-5MN32-0DL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5MN32-0DL0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2110-5MN32-0DL0 at 415 V?","answer":"At 415 V the breaking capacity is 121 kA, matching the rating at 440 V. This covers standard 400 V-class industrial distribution without needing a current-limiting upstream device."},{"question":"Where can I buy 3VA2110-5MN32-0DL0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment."},{"question":"Does 3VA2110-5MN32-0DL0 include phase failure protection?","answer":"Yes, phase failure detection is built into the motor protection design, so the breaker trips on a lost phase without requiring an external phase-monitor relay."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5MN32-0DL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5MN32-0DL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}