{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5MN36-0AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5MN36-0AH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5MN36-0AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5MN36-0AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-5MN36-0AH0, molded case circuit breaker, 3-pole, 100 A, motor protection design, 187 kA breaking capacity at 240 V.","salesMarkdown":"## Motor Protection MCCB — 100 A, Flat Derating Curve Breaking capacity reaches 187 kA at 240 V, stepping down to 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. ## Integration — Panel Fit and Auxiliary Switching Dimensions are 86 mm depth, 105 mm width, and 181 mm height. The trip alarm signals on thermal or magnetic trip — useful for remote fault indication on a motor control center (MCC) bucket. Phase failure detection is integrated; undervoltage release and ground-fault monitoring are not present on this variant.","metaTitle":"Siemens 3VA2110-5MN36-0AH0 SENTRON MCCB, 100 A, 3-Pole, Moto","metaDescription":"Siemens 3VA2110-5MN36-0AH0 SENTRON molded case circuit breaker, 100 A continuous, 3-pole, motor protection design, 187 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"17 s","Minimum":"4 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21105MN360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"30 000 W","operating power / at AC-3 / at 400 V":"55 000 W","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"E","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569374&mlfb=3VA2110-5MN36-0AH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5MN36-0AH0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2110-5MN36-0AH0 at 415 V?","answer":"121 kA at 415 V, which also applies at 440 V. At 240 V it is 187 kA."},{"question":"Will 3VA2110-5MN36-0AH0 drop into a panel specified for 3VA2116-5HL32-0AK0?","answer":"No — the 3VA2116-5HL32-0AK0 is a different frame size with a higher current rating. The 3VA2110-5MN36-0AH0 uses the 3VA2 frame at 100 A; the 3VA2116 frame is physically larger. Panel cutouts and busbar spacing differ."},{"question":"Where can I buy 3VA2110-5MN36-0AH0 and how is it quoted?","answer":"Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5MN36-0AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5MN36-0AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}