{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-5MN36-0HC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-5MN36-0HC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-5MN36-0HC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5MN36-0HC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-5MN36-0HC0, molded case circuit breaker, 3-pole, 100 A, motor protection design, shunt trip release, 2 auxiliary switches HQ.","salesMarkdown":"The Siemens SENTRON 3VA2110-5MN36-0HC0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current, holding that rating flat from 40 °C through 70 °C ambient — no derating needed in a warm enclosure. Interrupting capacity is 187 kA at 240 V, dropping to 121 kA at 415 V and 440 V, then 75.6 kA at 500 V, and 3.7 kA at 690 V. ## Auxiliaries and releases Comes fitted with 2 auxiliary switches (HQ type) and a shunt trip release. The shunt trip lets a safety PLC or E-stop circuit drop the breaker remotely — common for emergency-off zones or interlocked machine guards. ## Physical fit","metaTitle":"Siemens 3VA2110-5MN36-0HC0 SENTRON MCCB, 100 A, 3-Pole, Moto","metaDescription":"Siemens SENTRON 3VA2110-5MN36-0HC0 molded case circuit breaker, 100 A rated, 3-pole, motor protection design with shunt trip. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"17 s","Minimum":"4 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21105MN360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"30 000 W","operating power / at AC-3 / at 400 V":"55 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"E","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569389&mlfb=3VA2110-5MN36-0HC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-5MN36-0HC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-5MN36-0HC0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time, not a published figure."},{"question":"What is 3VA2110-5MN36-0HC0's interrupting capacity at 240 V?","answer":"187 kA at 240 V, which is high for a 100 A frame and gives good selectivity headroom in high-fault panels."},{"question":"Does this MCCB include a shunt trip?","answer":"Yes, it is fitted with a shunt trip (STL) auxiliary release for remote tripping, plus 2 HQ auxiliary switches."},{"question":"What compliance documentation does Siemens provide for 3VA2110-5MN36-0HC0?","answer":"As a current-production SENTRON MCCB, it carries CE, UL, and CSA certifications per Siemens standard documentation. RoHS and REACH declarations are available through Siemens support channels."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-5MN36-0HC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-5MN36-0HC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}