{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-6HK32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-6HK32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-6HK32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HK32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-6HK32-0AA0, molded case circuit breaker, 3-pole, 100 A, ETU340 electronic trip unit, 242 kA at 240 V, IP40 front.","salesMarkdown":"The Siemens SENTRON 3VA2110-6HK32-0AA0 is a 3-pole molded case circuit breaker rated for 100 A continuous at 40 °C, with the same rating holding flat all the way up to 70 °C — no derating needed in a warm cabinet. Breaking capacity hits 242 kA at 240 V, 187 kA at 415 V, and still holds 121 kA at 500 V; at 690 V it drops to 3.7 kA, so on a 690 V system you'd want to verify the available fault current stays under that. Power loss runs 10 W max at full load, which is manageable for thermal budgeting in a dense enclosure.","metaTitle":"Siemens 3VA2110-6HK32-0AA0 SENTRON MCCB, 100 A, 3-Pole, ETU3","metaDescription":"Siemens 3VA2110-6HK32-0AA0 SENTRON molded case circuit breaker, 100 A rated, 3-pole, ETU340 release. Breaking capacity 242 kA at 240 V. Active production, sourced to order. Request","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 500 A","Minimum":"1 500 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU340","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"ELISA LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=568886&mlfb=3VA2110-6HK32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HK32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-6HK32-0AA0 and how do I get a price?","answer":"This part is sourced through independent distribution. Submit an RFQ for current availability and pricing; it's quoted to order, not stocked on a shelf."},{"question":"What is 3VA2110-6HK32-0AA0's listed depth?","answer":"The depth is 86 mm (3.39 in), with a width of 105 mm (4.13 in) and height of 181 mm (7.13 in)."},{"question":"What compliance documentation does this brand provide for 3VA2110-6HK32-0AA0?","answer":"As a Siemens SENTRON product, the MCCB carries the standard IEC/UL certifications associated with the 3VA series. Specific RoHS, REACH, and UL documentation is available from the manufacturer upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-6HK32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-6HK32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}