{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-6HL32-0AF0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-6HL32-0AF0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-6HL32-0AF0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HL32-0AF0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-6HL32-0AF0, molded case circuit breaker, 3-pole, 100 A rated continuous current, 242 kA breaking capacity at 240 VAC, line protection design.","salesMarkdown":"The Siemens SENTRON 3VA2110-6HL32-0AF0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current, designed for line protection in distribution panels and industrial switchgear. Its breaking capacity reaches 242 kA at 240 VAC, 187 kA at 415 VAC and 440 VAC, 121 kA at 500 VAC, and 3.7 kA at 690 VAC — figures that give the specifying engineer substantial SCCR headroom for high-fault installations without cascading upstream. Dimensions are 181 mm high, 105 mm wide, and 86 mm deep — a standard MCCB footprint that fits most DIN-rail or panel-mount enclosures without rework. Power loss is 10 W maximum at rated current, a figure to include in enclosure thermal calculations when grouping multiple breakers. ## Ratings & Derating The 100 A continuous rating holds flat across the full ambient temperature range from 40 °C to 70 °C — no derating required up to the maximum operating temperature of 70 °C. Adjustable thermal-magnetic trip unit covers 150 A to 1 200 A, so the breaker can be tuned to protect downstream conductors or loads within that window. Storage range spans -40 °C to 80 °C; operating range is -25 °C to 70 °C.","metaTitle":"Siemens 3VA2110-6HL32-0AF0 SENTRON MCCB, 100 A, 242 kA at 24","metaDescription":"Siemens SENTRON 3VA2110-6HL32-0AF0 molded case circuit breaker, 100 A continuous, 3-pole, 242 kA breaking capacity at 240 VAC. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21106HL320AA0","Design Of The Auxiliary Switch":"1 auxiliary switch + 1 trip alarm switch HQ","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=497347&mlfb=3VA2110-6HL32-0AF0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HL32-0AF0/alternatives.json"},"ai":{"faq":[{"question":"Does this breaker include auxiliary contacts?","answer":"Yes, it ships with one auxiliary switch and one trip alarm switch (HQ type) pre-installed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-6HL32-0AF0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-6HL32-0AF0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}